Digital Inputs - GE Multilin 489 Instruction Manual

Generator management relay
Hide thumbs Also See for Multilin 489:
Table of Contents

Advertisement

CHAPTER 2: INTRODUCTION
2.2.4

Digital Inputs

489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
Courtesy of NationalSwitchgear.com
Time delay:
0.000 to 100.000 s in steps of 0.001
Pickup accuracy:
as per phase current inputs
Timing accuracy:
+50 ms at 50/60 Hz or ±0.5% total time
Elements:
Trip
RTDS 1 TO 12
Pickup:
1 to 250°C in steps of 1
Pickup hysteresis:
2°C
Time delay:
3 sec.
Elements:
Trip and Alarm
UNDERFREQUENCY
0.50 to 0.99 × rated voltage in Phase A
Required voltage:
Block from online:
0 to 5 sec. in steps of 1
Pickup level:
20.00 to 60.00 in steps of 0.01
Curve shapes:
1 level alarm, two level trip definite time
Time delay:
0.1 to 5000.0 sec. in steps of 0.1
Pickup accuracy:
±0.02 Hz
Timing accuracy:
±150 ms or ±1% of total time at 50Hz and 60Hz; ±300 ms or 2%
of total time at 25Hz
Elements:
Trip and Alarm
UNDERVOLTAGE
Pickup level:
0.50 to 0.99 × rated V in steps of 0.01
Curve shapes:
Inverse Time, definite time alarm
Time Delay:
0.2 to 120.0 s in steps of 0.1
Pickup accuracy:
as per voltage inputs
Timing accuracy:
±100 ms or ±0.5% of total time
Elements:
Trip and Alarm
VOLTAGE PHASE REVERSAL
Configuration:
ABC or ACB phase rotation
Timing accuracy:
200 to 400 ms
Elements:
Trip
VOLTS PER HERTZ
Pickup level:
1.00 to 1.99 × nominal in steps of 0.01
Curve shapes:
Inverse Time, definite time alarm
Time delay:
0.1 to 120.0 s in steps of 0.1
Pickup accuracy:
as per voltage inputs
Timing accuracy:
±100 ms at ≥ 1.2 × Pickup
±300 ms at < 1.2 × Pickup
Elements:
Trip and Alarm
FIELD BREAKER DISCREPANCY
Configurable:
assignable to Digital Inputs 1 to 7
Time delay:
0.1 to 500.0 s in steps of 0.1
Timing accuracy:
±100 ms or ±0.5% of total time
Elements:
Trip
2–11