Fault Setup; Test Output Relays - GE Multilin 489 Instruction Manual

Generator management relay
Hide thumbs Also See for Multilin 489:
Table of Contents

Advertisement

5.13.3 Fault Setup

FAULT

5.13.4 Test Output Relays

TEST
5–102
Courtesy of NationalSwitchgear.com
PATH: SETPOINTS
S12 489 TESTING
FAULT Iphase
[ ]
OUTPUT: 0.00 x CT
FAULT VOLTAGES
MESSAGE
PHASE-N: 1.00 x Rated
FAULT CURRENT
MESSAGE
LAGS VOLTAGE:
FAULT Iphase
MESSAGE
NEUTRAL: 0.00 x CT
FAULT CURRENT
MESSAGE
GROUND: 0.00 x CT
FAULT VOLTAGE
MESSAGE
NEUTRAL: 0 Vsec
FAULT STATOR
MESSAGE
RTD TEMP: 40°C
FAULT BEARING
MESSAGE
RTD TEMP: 40°C
FAULT OTHER
MESSAGE
RTD TEMP: 40°C
FAULT AMBIENT
MESSAGE
RTD TEMP: 40°C
FAULT SYSTEM
MESSAGE
FREQUENCY: 60.0 Hz
FAULT ANALOG
MESSAGE
INPUT 1: 0%
FAULT ANALOG
MESSAGE
INPUT 2: 0%
FAULT ANALOG
MESSAGE
INPUT 3: 0%
FAULT ANALOG
MESSAGE
INPUT 4: 0%
The values entered here are substituted for the measured values in the 489 when the
is "Simulate Fault".
SIMULATION MODE
PATH: SETPOINTS
S12 489 TESTING
FORCE OPERATION OF
[ ]
RELAYS: Disabled
CHAPTER 5: SETPOINTS
FAULT SETUP
Range: 0.00 to 20.00 × CT in steps of
0.01
Range: 0.00 to 1.50 × Rated in steps of
0.01. Enter as a phase-to-
neutral quantity.
Range: 0 to 359° in steps of 1
Range: 0.00 to 20.00 × CT in steps of
0.01. (180° phase shift with
respect to Iphase OUTPUT)
Range: 0.00 to 20.00 × CT in steps of
0.01. CT is either XXX:1 or
50:0.025
Range: 0.0 to 100.0 Vsec in steps of 0.1
Fundamental value only in
secondary volts
Range: –50 to 250°C in steps of 1
Range: –50 to 250°C in steps of 1
Range: –50 to 250°C in steps of 1
Range: –50 to 250°C in steps of 1
Range: 5.0 to 90.0 Hz in steps of 0.1
Range: 0 to 100% in steps of 1
Range: 0 to 100% in steps of 1
Range: 0 to 100% in steps of 1
Range: 0 to 100% in steps of 1
TEST OUTPUT RELAYS
Range: Disabled, 1 Trip, 2 Auxiliary,
3 Auxiliary, 4 Auxiliary, 5 Alarm,
6 Service, All Relays, No Relays
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL