Toshiba V Series User Manual page 199

Sequence controllers
Hide thumbs Also See for V Series:
Table of Contents

Advertisement

(5) Self-check of duplex configuration
Check item
Tracking
receive error
Equalize
receive error
Partial
equalize
receive error
Timeout for
completion of
equalize
receive
Timeout for
completion of
tracking
receive
Remote CPU
module error
Power outage
at remote
system
Broken cable
for tracking
monitor
Broken cable
for tracking
transmission
Primary/
Secondary
switch setup
error
Duplex
software
status error
Duplex
hardware
status error
6F8C0836
Table 6-7 Self-check of duplex configuration
Operation when error is
Self-check
Online
controller
Standby controller
Single
detected a tracking
operation
receive error.
mode
The controller
Single
receiving equalize
operation
has detected a
mode
receive error.
The controller
Single
receiving partial
operation
equalize has
mode
detected a receive
error.
The controller
Single
receiving equalize
operation
has detected timeout
mode
for equalize receive.
The controller
Single
receiving tracking
operation
has detected timeout
mode
for tracking receive.
Has detected error
Single
down of the remote
operation
CPU module.
mode
Has detected power
Single
outage of the remote
operation
system.
mode
Has detected broken
Single
cable for tracking
operation
monitor.
mode
Error down at both sides
when RUN is requested
from HOLD mode.
Has detected broken
Single
cable for tracking
operation
transmission.
mode
Error down at both sides
when RUN is requested
from HOLD mode.
Has detected mode
Error down Error down Set the primary and secondary
switch setup error in
the expansion
interface module.
Has detected duplex
Single
software status parity
operation
error.
mode
Has detected duplex
Single
hardware status
operation
parity error.
mode
detected
Operator action
Standby
controller
Error down Check connection of the
expansion interface module,
and tracking transmission/
monitoring cables, and restart
Error down
the system.
Error down
Error down
Error down
Error down Correct the remote CPU
module error, and restart the
system.
power
Power up the remote system.
outage
Error down Check cables to connectors
and internal breakage of
cables, and restart the system.
Error down
power supplies at both
systems so that they donÅft
overlap, and restart the
system.
Error down Check installation of the S2
module, expansion interface
and module base, and restart
the system.
Error down
6.8 RAS Function
6
177

Advertisement

Table of Contents
loading

This manual is also suitable for:

2000

Table of Contents