Siemens SIMATIC Manual page 360

Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Analog modules
6.7 Analog input module SM 331; AI 8 x 12 bit;(6ES7331-7KF02-0AB0)
Technical specifications
additional conversion time for wire-break monitoring in ms
or
additional conversion time for resistance measurements and
wire-break monitoring in ms
Resolution in bits (including overrange)
Interference frequency suppression at interference fre-
quency f1 in Hz
Basic execution time of the module in ms (all channels
enabled)
Measured value smoothing
Interference frequency suppression, error limits
Interference frequency suppression at F = n (f1 ± 1 %), (f1 = interference frequency)
Common mode interference (V
Seriesmode interference (peak interference value < rated
input range)
Crosstalk between inputs
Operational limit (across entire temperature range, relative to the measurement range end value in the selected input
range)
Voltage input
Current input
Resistance
Thermocouple
Resistance thermometer
Basic error limit (operational limit at 25 °C, relative to the measurement range end value in the selected input range)
Voltage input
Current input
Resistance
Thermocouple
Resistance thermometer
Temperature error (relative to input range)
Linearity error (relative to input range)
Repeat accuracy (in settled state at 25 °C, relative to input
range)
Temperature error of internal compensation
360
< 2.5 V)
CM
10
10
16
16
9 bits
12 bits
400
60
24
136
none
> 70 dB
> 40 dB
> 50 dB
80 mV
250 mV to 1,000 mV
2.5 V to 10 V
3.2 mA to 20 mA
150 Ω; 300Ω; 600 Ω
Types E, N, J, K, L
Pt 100/Ni 100
Pt 100 Klima
80 mV
250 mV to 1,000 mV
2.5 V to 10 V
3.2 mA to 20 mA
150 Ω; 300 Ω; 600 Ω
Types E, N, J, K, L
Pt 100/Ni 100
Pt 100 Klima
± 0.005%/K
± 0.05 %
± 0.05 %
± 1 %
10
10
16
16
12 bits
14 bits
50
10
176
816
± 1 %
± 0.6 %
± 0.8 %
± 0.7 %
± 0. 7 %
± 1. 1 %
± 0. 7 %
± 0. 8 %
± 0.7 %
± 0.4 %
± 0.6 %
± 0.5 %
± 0.5 %
± 0.7 %
± 0.5 %
± 0.6 %
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ

Advertisement

Table of Contents
loading

This manual is also suitable for:

S7-300S7-300 module data