Firmware update
This is how you update the firmware of a central or distributed module:
1. Select the module SM 322; DO 16 x DC 24V/0.5 A in HW-config.
2. Select PLC > Update Firmware.
3. Use the "Browse" button to select the path to the firmware files (*.upd).
4. Click the "Run" button.
– The module performs the firmware update.
5. You can find additional information in the STEP 7 Online Help.
Note
• During the firmware update, the OB 83 (alarm due to removing and inserting
• If the red LED (SF) on the module blinks, an error occurred during the firmware update
• A firmware update through HW-config is not permitted if the module is in redundant
Identification of the firmware version
After the firmware update, you must label the firmware version on the module.
3.24.4
I&M identification data
Properties
I data: Information about the module, which is normally found on the module casing. I-data is
write-protected. They include:
● Hardware release status
● Firmware release status
● Serial number
M data: System-dependent information (e.g. plant designation).
M data is created during configuration.
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
3.24 Digital output module SM 322; DO 16 x DC 24 V/0.5 A: (6ES7322-8BH10-0AB0)
modules), the OB 85 (program execution error) and the OB 86 (error due to module
rack failure) are opened. If the diagnostics alarm of the module is approved, the OB 82
(diagnostics alarm) will also be opened during the firmware update. Make sure that the
OB is set correspondingly.
and the update must be repeated. In this case, the bootloader version Ex.x.x is
displayed in the online diagnostics.
mode.
Digital modules
155