Siemens SIMATIC Manual page 267

Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Representation of the analog values of Pt x00 GOST (0.003910) standard resistance thermometers
Table 5- 12
Representation of the analog values of Pt 10, 50, 100, 500 GOST (0.003910) standard resistance thermome-
ters
Pt x00 GOST
Units
Standard in °C
dec
(1 digit =
0.1°C)
> 1295.0
32767
1295.0
12950
:
:
1100.1
11001
1100.0
11000
:
:
-260.0
-2600
-260.1
-2601
:
:
-273.2
-2732
< - 273.2
-32768
Representation of analog values for Pt x00 and Pt x0 GOST (0.003850 and 0.003910) climatic
resistance thermometers
Table 5- 13
Representation of analog values for Pt 100, 200, 500,1000 and Pt 10, 50, 100, 500 GOST (0.003850 and
0.003910) climatic resistance thermometers
Pt x00 climat-
Units
ic/GOST in °C
dec
(1 digit = 0.01
°C)
> 155.00
32767
155.00
15500
:
:
130.01
13001
130.00
13000
:
:
-120.00
-12000
-120.01
-12001
:
:
-145.00
-14500
< - 145.00
-32768
S7-300 Module data
Manual, 06/2017, A5E00105505-AJ
Pt x00 GOST
Standard in
hex
°F (1 digit =
0.1 °F)
7FFF
> 2363.0
H
3296
2363.0
H
:
:
2AF9
2012.1
H
2AF8
2012.0
H
:
:
F5D8
-436.0
H
F5D7
-436.1
H
:
:
F554
-459.7
H
8000
< - 459.7
H
Pt x00
climat-
hex
ic/GOST in
°F (1 digit =
0.01 °F)
7FFF
> 311.00
H
3C8C
311.00
H
:
:
32C9
266.01
H
32C8
266.00
H
:
:
D120
-184.00
H
D11F
-184.01
H
:
:
C75C
-229.00
H
8000
< - 229.00
H
5.1 Representation of the values for analog input channels
Units
Range
dec
hex
32767
7FFF
Overflow
H
23630
5CE4
Overshoot range
H
:
:
20121
4E99
H
20120
4E98
Rated range
H
:
:
-4360
EEF8
H
-4361
EEF7
Undershoot range
H
:
:
-4597
EE0B
H
-32768
8000
Underflow
H
Units
Range
dec
hex
32767
7FFF
Overflow
H
31100
797C
Overshoot range
H
:
:
26601
67E9
H
26600
67E8
Rated range
H
:
:
-18400
B820
H
-18401
B81F
Undershoot range
H
:
:
-22900
A68C
H
-32768
8000
Underflow
H
Principles of analog modules
267

Advertisement

Table of Contents
loading

This manual is also suitable for:

S7-300S7-300 module data

Table of Contents