Advertisement

Communication
11.3 Communication via PROFINET IO
11.3.9.4

PROFIenergy measured values

Table 11- 18 Overview of the PROFIenergy measured values
PROFIenergy
PROFIenergy
measured
measured
value ID
value
34
Active power
166
Power factor
200
Active energy
import
11.3.9.5

PROFIenergy energy-saving mode

SINAMICS S120 drive devices support the PROFIenergy energy-saving mode 2. The
following two parameters indicate the effective PROFIenergy mode:
● Parameter r5600 indicates the currently active PROFIenergy mode.
● Using interconnectable bits, the r5613 parameter indicates whether the PROFIenergy
energy saving is active.
The energy-saving mode can activated or deactivated for S120 drive devices using the
PROFIenergy control commands (see also PROFIenergy commands (Page 748)).
The active energy-saving mode is indicated with alarm A08800.
The energy-saving mode also remains active in SINAMICS S120 drive units with the
following events:
● PROFINET disconnection
● CPU goes to STOP
● Error in the backplane bus
While the PROFIenergy energy-saving mode is active all diagnostics alarms are switched off
in SINAMICS. These alarms are therefore not sent during energy-saving mode.
11.3.9.6

Block PROFIenergy

For SINAMICS S120 drive devices, the parameter setting p5611.0 = 1 can be used to block
PROFIenergy. This causes the control commands to be ignored.
750
Unit
SINAMICS
SINAMICS
source
source
parameters
parameters
Name
W
r0032
Active power
smoothed
1
r0038
Smoothed power
factor
Wh
r0039[1]
Energy accepted
PROFIenergy accuracy Value range
Domain
Class
1
12
1
12
2
11
Function Manual, (FH1), 04/2014, 6SL3097-4AB00-0BP4
Largest value for
r2004 of all drive
objects
0 ... 1
-
Drive functions

Hide quick links:

Advertisement

Table of Contents