Configuring the F-CPU in HW Config
1. Different than for a drive control, now select a PROFIsafe-compatible controller, for
2. To establish the communication, select PROFINET IO again.
Figure 11-49 PROFIsafe controller configuration
3. In HW Config, click "Station\Save and compile".
4. Click the S120 component in the drive control window.
5. Start copying with "Edit\Copy".
6. Return to the HW Config window of the PROFIsafe controller.
7. Right-click the PROFINET line.
Drive functions
Function Manual, (FH1), 04/2014, 6SL3097-4AB00-0BP4
example, a CPU 317F-2 PN/DP.
We have manually renamed the PROFIsafe controller to "F-CPU".
11.3 Communication via PROFINET IO