Siemens SICAM Q80 System Manual page 51

Power quality recorder
Hide thumbs Also See for SICAM Q80:

Advertisement

Notifications
In response to certain events, the measurement device can both list them in the
messages
about them.
220
By means of the option Voltage event, the value limits set are activated for the purpose of sending event
messages. It is also possible to send messages cyclically or in response to when the free(memory) space falls
below a minimum set by the user.
Using the option UDP data storage state, the measurement device can cyclically send messages about
concluded data measurements. The message contains the device ID as well as information about the
measurements concluded, so that in the case of successive measurements, it is possible to determine whether
new measured data is available for retrieval. The User Datagram Protocol (abbreviated UDP) is a minimalist,
connectionless network protocol belonging to the Transport layer of the Internet protocol family.
The message recipient must be specified:
IP-address: Address of the PC which is to receive the message.
Port: Recipient target port
Time interval: Sending interval in minutes. The specifications are made either by means of the pop-down
list or by manual entry.
Example: Sending a message every 10 min:
IP-Address: 10.0.2.10; Port: 1205; Time interval: 10 min
Note
UDP is also used by the supplemental program
program is able to directly adopt the device information (name, serial number and IP-address).
Operation modes and settings
Events - Notifications
Auto-Transfer
Power Quality Recorder SICAM Q80 7KG8080, System manual
Event Table
and
send
73
. For this reason, the transfer
144
E50417-H1076-C420-A2, Release 12.01.2015
51