Figure 2-63. Change Default Gateway Ip Address Screen - Siemens A53457 Installation & Maintenance

Wayside access gateway wag
Table of Contents

Advertisement

If the Default Gateway is configured for Disabled, then Ethernet messages that are addressed to IP
devices that are not on the subnet configured for the WAG will be discarded by the WAG since
the destination IP device is considered unreachable.
Often, Default Gateways are bridges, routers, or some other device on the LAN that maintains its
own route tables so that it knows how to forward Ethernet messages into and between subnets.
This Default IP Gateway value default is: Disabled.
To change the Default Gateway IP Address:
1.
On the Second Configuration Menu, select "Default IP Gateway" Address to be changed. The
Change Default Gateway IP Address screen appears.

Figure 2-63. Change Default Gateway IP Address Screen

2.
From the screen in figure 2-63, do one of the following:
a. To disable the Default Gateway IP Address enter 0 (zero) in the first data field and then
press ENTER. The user will be returned to the Second Configuration Menu. Go to step 3.
b. To leave the first data field of the current IP Address unchanged, press ENTER.
c. To change the first data field of the IP Address, type the digit(s) and then press ENTER.
Entry can be any value from 1 to 255.
d. Repeat step b or c above for each of the four data fields. After the fourth data field is
filled, the user will be returned to the Second Configuration Menu. Go to step 3.
3.
Prior to exiting the First Configuration Menu, select "Save changes then restart" to save
changes and restart the WAG.
Document No.: COM-00-05-16
Version: C.1
INSTALLATION AND CONFIGURATION
2-47
June 2006, Revised June 2014