Siemens SINUMERIK 810DE powerline Equipment Manual page 43

Sinumerik 810d configuration ccu
Hide thumbs Also See for SINUMERIK 810DE powerline:
Table of Contents

Advertisement

Mounting the
The metal sheet is mounted on the 3-axis CCU box with the 3 screws on the
shielding plate
underside (2-axis CCU box, see figure Mounting the shielding plate). The shiel-
ding plate is supplied in the box. The tube clip for connecting the shield is con-
tained in the scope of supply of the ready-assembled SIEMENS motor cable.
130
Cooling
clearance
100 mm
Fig. 3-4
Dimension drawing of the 3-axis CCU box
Copyright © Siemens AG 2006
SINUMERIK 810D Equipment Manual Configuration CCU (PHC) – 03/2006 Edition
Cooling clearance 100 mm
The tightening
torque must be
complied with
when mounting
modules!!
M3: 0.8 Nm
M4 : 1.8 Nm
M5 : 3 Nm
M6 : 6 Nm
Motor connection
A3
A2
A1
288
Shielding plate
3 Design and Installation of the 810D
3.2 Assembly of the SINUMERIK 810D
Additional connection option
for shield connection M5x10
25
100
150
Equipotential bonding terminal
3-41