Siemens Milltronics BW500 Operating Lnstructions
Hide thumbs Also See for Milltronics BW500:
Table of Contents

Advertisement

Integrators
Milltronics BW500 and BW500/L
Operating Instructions 12/2010
Milltronics

Advertisement

Table of Contents
loading

Summary of Contents for Siemens Milltronics BW500

  • Page 1 Integrators Milltronics BW500 and BW500/L Operating Instructions 12/2010 Milltronics...
  • Page 2 The user is responsible for all changes and repairs made to the device by the user or the user’s agent. • All new components are to be provided by Siemens Milltronics Process Instruments. • Restrict repair to faulty components only.
  • Page 3: Table Of Contents

    Table of Contents Safety Notes .............................1 The Manual ...............................1 Technical Support ............................2 Milltronics BW500 and BW500/L ..................3 Milltronics BW500 ...........................3 Milltronics BW500/L ..........................3 Milltronics BW500 and BW500/L features ..................3 Specifications ........................5 Installation ........................... 9 Dimensions ...............................9 Layout ..............................11 Optional Plug-ins ...........................12...
  • Page 4 PROGRAM Mode Display ......................29 To enter PROGRAM mode: .......................29 RUN Mode ............................31 Initial Start Up ............................31 Power Up ............................31 Programming ..........................31 Press ..............................32 Load Cell Balancing ..........................35 Typical two load cell belt scale ....................35 Zero Calibration ...........................38 RUN Mode ............................40 Recalibration ........................41 Belt Speed Compensation ........................41 Material Tests ............................42...
  • Page 5 Setup and Tuning ...........................74 Proportional Control (Gain), ....................74 Integral Control (Automatic Reset), I ..................75 Derivative Control (Pre-Act or Rate), D ..................76 Feed Forward Control, F ......................76 PID Setup and Tuning ...........................77 Initial Start-Up ..........................77 Programming ............................80 Batching ..........................83 Connections ............................84 Typical Ladder Logic ........................84 Programming ............................84 Operation ..............................85...
  • Page 6 Proportional Integral Derivative (PID) Control Parameters (P400 – P419) ......130 Batch Control (P560 – P568) ......................134 Totalization (P619 - P648) ........................136 ECal Parameters (P693 – P698) ......................141 Communication (P740 - P799) ......................143 SmartLinx Hardware Testing ......................143 Test and Diagnostic (P900 - P951) ....................145 Troubleshooting .......................
  • Page 7: Safety Notes

    The Manual Note: • The Milltronics BW500 and BW500/L are to be used only in the manner outlined in this instruction manual. • These products are intended for use in industrial areas. Operation of this equipment in a residential area may cause interference to several frequency based communications.
  • Page 8: Technical Support

    Technical Support Support is available 24 hours a day. To find your local Siemens Automation Office address, phone number and fax number go www.siemens.com/automation/partner • Click on the tab Contacts by Product then find your product group (+Process Automation > +Process Instrumentation > +Level Measuring Instruments).
  • Page 9: Milltronics Bw500 And Bw500/L

    LCD, or as output in the form of analog mA, alarm relay and remote totalization. Milltronics BW500/L The Milltronics BW500/L is an integrator for use in basic belt scale or weighbelt applications. The speed and load signals from the conveyor and scale, respectively, are processed to derive rate of material flow, and totalization.
  • Page 10 PID control batch control multispan operation moisture compensation fixed incline compensation fixed differential speed detection The optional mA I/O board is required for 3 outputs: PID control, moisture, and incline compensation. Page 4 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 11: Specifications

    • fuse, FU1 2AG, Slo Blo, 2 A, 250 V or equivalent Application • compatible with Siemens belt scales or equivalent 1, 2, 4, or 6 load cell scales (1 or 2 load cell scales for BW500/L) • compatible with LVDT equipped scales, with use of optional interface board Accuracy •...
  • Page 12 • open collector switch rated 30 V DC, 100 mA max remote totalizer 2 • contact closure 10 - 300 ms duration • open collector switch rated 240 V AC/DC, 100 mA max Not available with BW500/L. Page 6 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 13 Belden 8760, 1 pair, twisted/shielded, 18 AWG, 300 m (1000 ft.) max. Options Speed Sensor Siemens MD-36/36A/256 or 2000A, RBSS, TASS, WS100, or WS300, or compatible Dolphin Plus Siemens Windows®based software interface (refer to associated product documentation) SmartLinx®Modules...
  • Page 14 Legal for US Trade - NTEP approved Legal for European Trade - MID approved Legal for International Trade - OIML approved EMC performance available upon request Not available with BW500/L. Page 8 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 15: Installation

    Installation Note: • Installation shall only be performed by qualified personnel and in accordance with local governing regulations. • This product is susceptible to electrostatic shock. Follow proper grounding procedures. Dimensions 209 mm (8.2") 16 mm (0.6") lid screws 92 mm 172 mm (6 pieces) (3.6")
  • Page 16 Recommended mounting: directly to wall or to electrical cabinet back panel • Recommended mounting screws: #6 • If alternate mounting surface is used, it MUST be able to support four times the weight of the unit. Page 10 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 17: Layout

    Layout optional SmartLinx module port 3 (RJ-11) battery, memory back up certification switch power optional switch Analog I/O board fuse 1. Applicable for trade approvals 2. Not available for BW500/L 3. To reduce communication interference, route SmartLinx®cable along right side of enclosure wall.
  • Page 18: Optional Plug-Ins

    Optional Plug-ins SmartLinx Module BW500 and BW500/L is software/hardware ready to accept the optional Siemens SmartLinx® communications module that provides an interface to one of several popular industrial communications systems. BW500 and BW500/L may be shipped to you without a SmartLinx®module, for installation at a later date.
  • Page 19 Installation 1. Isolate power and voltages applied to the BW500 2. Open the lid 3. Install the board by mating the connectors and secure the card in place using the three screws provided 4. Close the lid 5. Apply power and voltage to the BW500 Refer to: Specifications •...
  • Page 20: Interconnection

    Siemens Milltronics Dolphin Plus, print data, or Modbus ASCII or RTU protocol Typical system capability. Not all components or their maximum quantity may Note: be required Page 14 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 21: Scale - One Load Cell

    Colour code for load cells used on Note: junction box Siemens weighfeeders may be different than shown. Please refer to the weighfeeder wiring diagram. *Where separation between the BW500 and BW500/L and belt scale exceeds 150 m (500 ft.), or legal for trade certification:...
  • Page 22: Scale - Two Load Cells

    BW500 and BW500/L terminal 12 to scale `red' BW500 and BW500/L terminal 13 to scale `blk' If the load cell wiring colours vary from those shown, or if extra wires are provided, consult Siemens. Page 16 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 23: Scale - Four Load Cells

    BW500 terminal 12 to scale `red' BW500 terminal 13 to scale `blk' If the load cell wiring colours vary from those shown, or if extra wires are provided, consult Siemens. Not available with the BW500/L. 7ML19985DK05Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS...
  • Page 24: Scale - Six Load Cells

    BW500 terminal 12 to scale `red' BW500 terminal 13 to scale `blk' If the load cell wiring colours vary from those shown, or if extra wires are provided, consult Siemens. Not applicable for the BW500/L. Page 18 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 25: Scale - Lvdt

    BW500 and BW500/L terminal 11/12 and 13/14 run additional conductors from: BW500 terminal 12 to integrator terminal block ‘+EXC’ BW500 terminal 13 to integrator terminal block ‘-EXC’ For further connection information on specific LVDTs consult Siemens. 7ML19985DK05Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS Page 19...
  • Page 26: Speed

    Input device in the form of open collector transistor or dry contact across BW500 and BW500/L terminals 16 / 17 will also serve as a suitable speed signal. If a speed sensor other than the models shown is supplied, consult with Siemens for details.
  • Page 27: Auxiliary Speed Sensor

    Input device in the form of open collector transistor or dry contact across BW500 terminals 24-28 will also serve as a suitable speed signal. If a speed sensor other than the models shown is supplied, consult with Siemens. Not available for BW500/L.
  • Page 28: Auxiliary Inputs

    P270 Refer to on page 122 for programming details. Auto Zero Prefeed activated dry contact Auto Zero Refer to on page 47. RS-232 Port 1 Printers Printer receive common Page 22 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 29: Computers And Modems

    Computers and Modems For connection to a PC compatible computer or modem, using no flow control, typical configurations are: DB-9 DB-25 Remote Totalizer supply, 30 V max remote totalizer 1 supply, 240 V max remote totalizer 2 External power supply not required on all totalizer models. Note: mA Output 1 to customer instrumentation,...
  • Page 30: Relay Output

    Relay Output Relays shown in de-energized state, contacts normally open, rated 5 A at 250 V non- inductive. BW500/L has relay 1 and 2 only Page 24 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 31: Port 2

    RS-485 Port 2 Daisy Chain customer device Terminal Device customer device RS-232 Port 3 Jumper pins 4-6 and 7-8 when using hardware flow control. Otherwise, leave Note: them open. 7ML19985DK05Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS Page 25...
  • Page 32: Power Connections

    100 / 115 / 200 / 230 V 50 / 60 Hz select voltage via switch Page 26 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 33: Ma I/O Board Connections

    mA I/O Board connections auxiliary supply output, isolated 24 V DC at 50 mA, short circuit protected from customer instrumentation, isolated mA input, 200 from customer instrumentation, isolated mA input, 200 to customer instrumentation, isolated mA output, 750 maximum load to customer instrumentation, isolated mA output, 750...
  • Page 34: Start Up

    PROGRAM mode initiates calibration initiates calibration clears entry toggles between view and edit modes, confirms parameter val- opens RUN mode changes RUN mode display starts totalizer 1 reset sequence Page 28 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 35: Program Mode

    PROGRAM Mode The PROGRAM parameters define the calibration and operation of the BW500 and BW500/L. In PROGRAM mode, the user can view the parameter values or edit them to suit the application. PROGRAM Mode Display VIEW P001 Language 1-Eng 2-Fra 3-Deu 4-Esp EDIT P001 Language 1-Eng 2-Fra 3-Deu 4-Esp...
  • Page 36 To reset a parameter value Press From the edit mode P011 Design Rate: Enter Rate 100.00 kg/h Press Value is reset to factory value. P011 Design Rate: e.g. 0.00 kg/h Enter Rate 0.00 kg/h Page 30 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 37: Run Mode

    RUN Mode To operate BW500 and BW500/L in the RUN mode, the unit must undergo an initial programming to set up the base operating parameters. Attempting to enter the RUN mode without satisfying the program requirements forces the program routine to the first missing item. Initial Start Up Initial start up of BW500 and BW500/L consists of several stages, and assumes that the physical and electrical installation of the belt scale and speed sensor, if used, is complete:...
  • Page 38: Press

    00-00-00 Press factory design rate P011 Design Rate: Enter Rate 0.00 t/h Press P011 Design Rate: e.g. rate of 100 t/h Enter Rate 0.00 t/h Not applicable for the BW500/L Page 32 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 39 Press factory design speed P014 Design Speed Enter Speed 0.00 m/s Press P014 Design Speed e.g.speed of 0.8 m/s Enter Speed 0.00 m/s Press P015-01 Speed Constant Pulses/m 0.0000 If the speed input is configured for constant speed, display value reads ‘Jumpered’ press to advance.
  • Page 40 Enter test load This value is calculated. For manual or automatic calculation, refer to P680 on page 139. The test load value should be less than the design load (P952). If not, contact Siemens. Page 34 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 41: Load Cell Balancing

    4 Select: 1-A&B, 2-C&D Press Load Cell Balancing A & B Place weight at cell B and press ENTER For six load cell configurations contact your local Siemens representative. 7ML19985DK05Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS Page 35...
  • Page 42 P295 Load Cell Balancing: Select: 1-A&B, 2-C&D Press P295 Load Cell Balancing: Select: 1-A&B, 2-C&D Press Load Cell Balancing C & D Place weight at cell D and press ENTER. Page 36 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 43 ’ A ’ ’B’ ’C’ ’D’ test weight Press Load Cell Balancing C & D Place weight at cell C and press ENTER. ’ A ’ ’B’ ’C’ ’D’ test weight Press Balancing the load cells requires a subse- Load Cell Balancing C & D quent zero and span recalibration Load cells are now balanced.
  • Page 44: Zero Calibration

    Refer to on page 155. With the conveyor stopped and locked out, apply the test weight or chain to the scale as instructed in the associate manuals; then start the conveyor. Page 38 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 45 Press the current span count Span Calibration Current Span Setup test Press ENTER to Start Press the span count being calculated while cali- Initial Span Calibration in progress bration is in progress Current Reading #### The duration of the Span calibration is dependent on speed (P014), length (P016), and revolutions (P360) of the belt.
  • Page 46: Run Mode

    Once the initial programming is complete and the BW500 and BW500/L is operating in the RUN mode, you may now put the belt conveyor into normal service. The BW500 is functioning under its initial program and calibration, reporting rate of material flow and totalizing. Page 40 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 47: Recalibration

    Recalibration Belt Speed Compensation To achieve optimum accuracy in the rate computation, the belt speed displayed must equal that of the actual belt speed. As the speeds are likely to differ, a belt speed compensation should be performed. Run the conveyor with the belt empty. View the belt speed.
  • Page 48: Material Tests

    Resume normal operation. If the span adjust value is not acceptable, repeat the material test to verify repeatability. If the result of the second material test differs considerably, consult Siemens or contact your local Siemens representative.
  • Page 49 (BW500 – material sample weight) x 100 % span adjust = material sample weight start total scale stop total scale Access P019 and enter EDIT mode P019 Manual Span Adjust Select 1-% Change 2-Material Test Press P598 Span Adjust Percentage Enter Calculated +/- error 0.00 Press...
  • Page 50: Material Test

    Material Test Deviation -1.19 as a % of the actual weight Accept 0-No, 1-Yes Press e.g. the new test load value is displayed. P017 Test Load Weight: MS1 Enter Test Load 56.78 Page 44 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 51: Design Changes

    Verify the results of the span adjust by material test or return to normal operation. Design Changes Where parameters have been changed with a resultant impact on the calibration, they do not take effect until a recalibration is done. If significant changes have been made, an initial zero (P377) and/or initial span (P388) may be required (see page 128).
  • Page 52: Initial Zero

    Press ENTER to accept value 551413 if unacceptable, press to restart Press e.g. the current zero count Zero Calibration. Current Zero 551413 Clear belt. Press ENTER to start Page 46 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 53: Direct Zero

    This is the end of zero calibration. Proceed with span recalibration or return to Note: RUN. Direct Zero Use direct zero entry (P367) when replacing software or hardware, if it is not convenient to perform an initial zero. A record of the last valid zero count is required. Access P367 and enter EDIT mode P367 Direct Zero Entry Enter Zero Count...
  • Page 54: Routine Span

    <10% of design (P014) Calibration aborted Belt speed is too low: During this step the progress of the process will be shown on the display with a progress indicator in % Page 48 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 55: Initial Span

    Calibration is out of range Deviation Error: XX.XX This indicates that the mechanical system is errant. The use of P388, initial span, should be used judiciously and only after a thorough mechanical investigation has been exercised. Find and rectify the cause of the increased or decreased deviation. Then re-try a span recalibration.
  • Page 56: Direct Span

    In the case of different feeder locations, a span calibration may be required to match each feedpoint or combination of feedpoints. Not available with BW500/L. Page 50 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 57 Each time one of the eight conditions is in effect, the corresponding multispan is selected prior to putting the BW500 into the RUN mode. The selection is made by either changing the multispan operation number, accessed via P365, or by external contacts connected to the Auxiliary input, and programmed via P270.
  • Page 58 MS 2 e.g. if there is no material on the belt and Total 1: 0.00 kg the conveyor is running. The current rate is 0 and no material has been totalized. Page 52 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 59: Online Calibration

    When the material to be run on the belt changes, the multispan is changed to the corresponding span. This is completed either by changing the span value entered in P365, or by closing the appropriate contacts connected to the programmed Auxiliary inputs. Multispan Auxiliary Input Multispan...
  • Page 60 Enter Reference Weight 10.000 Enter the max., high, and low limit setpoints as a percentage in P357. Press Access limit as a percentage P357-01 Online Calibration Limits MAX Limit: 90.0 Press Page 54 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 61 Access P357-02 Online Calibration Limits HIGH Limit: 70.0 Press Access P357-03 Online Calibration Limits LOW Limit: 30.0 Calibrate the mA inputs on the BW500 to the 4 and 20 mA levels of the weigh bin. 4 mA is calibrated with the weigh bin empty, using P261-01 or –02. 20 mA is calibrated with the weigh bin full, using P262-01 and P262-02.
  • Page 62 Calibration in progress RLY 1 When the Low limit (30%) is reached, the totalizer is deactivated and the assigned relay is de-energized, which reopens the material feed to the weigh bin. Page 56 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 63 The BW500 Online material total, the amount of material totalized between the High and Low limits, is compared to the value entered in P356. The deviation percentage between these values and the new Span count value is displayed. deviation percent Online Calibration - Deviation 2.51%...
  • Page 64: Factoring

    Factoring is complete. Remove test weight and return to RUN mode if desired. If multispan function is used, the test load value is stored for the current Note: multispan only. Page 58 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 65: Linearization

    Linearization Conveyor applications where the ideal belt scale location has been compromised, or where there is a high degree of variation in belt tension, typically cause the belt scale to report load non-linearly. The BW500 and BW500/L provides a linearizing function (P390 - P392) to correct for the deficiency in the weighing system and to provide an accurate report of the actual process.
  • Page 66 BW500 total compensation kg/m tonnes tonnes 6.94 -10.7 13.89 11.1 20.83 -5.1 27.78 10.0 34.72 12.5 13.3 -6.0 calculation example: % compensation = [(2.5 – 2.8) x 100]/2.8 Page 60 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 67 = - 10.7  -6.0 actual weight per material test totalized weight by BW500  belt scale response  -5.1 linearized BW500 response internal response 100% - 150% of span  11.1 % compensation  span (100%) -10.7 Load - kg/m Program the BW500 as follows: Parameter Function...
  • Page 68 BW500 response internal response 100% - 150% of span % compensation span (100%)  -10.7 Load - kg/m For Parameter reference, go to Parameters on page 111. Page 62 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 69: Operation

    Operation Load Sensing For the BW500 and BW500/L to calculate rate and totalize material flow along the belt conveyor, a load signal representative of weight of material on the belt is required. The load signal is provided by the belt scale. The BW500 and BW500/L is compatible with belt scales fitted with 1, 2, 4, or 6 strain gauge type load cells.
  • Page 70: Moisture Compensation

    The BW500/L allows for a fixed moisture content to be entered. See “P398-01 Moisture Content” on page 129. Page 64 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 71: Incline Compensation

    Example: Setting P398-02 = 30% will allow the 4 - 20 mA input to correspond to 0 - 30% moisture. The Zero and Span calibration is not affected by the presence of a moisture meter. It is understood that the calibrations are performed using dry static weights. The Moisture Meter must be connected to the appropriate mA input and programmed as described in the following steps: Enable mA input function for moisture compensation P255-01 or 02 = 4 (moisture...
  • Page 72: Damping

    22 mA maximum (P212 and P213 respectively). The output 4 and 20 mA levels can also be trimmed (P214 and P215 respectively) to agree with a milliammeter or other external mA device. Page 66 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 73: Relay Output

    The mA output value can be tested to output a prescribed value using parameter P911. P911 Refer to on page 145. The optional mA I/O board provides two additional mA outputs , programmable as outputs 2 and 3, using the same parameters as the standard output (1). If programmed for PID control, output 2 is assigned to PID control loop 1 and output 3 is assigned to PID control loop 2.
  • Page 74: Totalization

    Totalizer resolution or count value is set by the respective internal (P631) and external (P638) totalizer resolution parameters. If the resolution selected causes the totalizer to lag behind the count rate, the next possible resolution is automatically entered. Page 68 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 75 Example: Internal totalizer 1 Given: P005 = 1 (t/h) P631 = 4 Then: totalizer count increments by 10 for each 10 metric tonnes registered External totalizer 1 Given: P005 = 1 (t/h) P638 = 5 Then: contact closure occurs once for every 10 metric tonnes registered For remote totalization, the contact closure duration (P643) is automatically calculated upon entry of the design rate (P011) and remote totalizer (P638) parameters, so that the duration of contact closure allows the relay response to track the total up to 150% of the...
  • Page 76 RUN mode resets internal totalizer 1 Placing the internal totalizers on to the display scroll of the RUN mode is controlled by the totalizer display parameter (P647); displaying either one or both totalizers. Page 70 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 77: Pid Control

    PID Control The PID control algorithm in the BW500 is designed specifically to work for feed rate control applications. It is based on motor control type algorithms and includes several anti-wind up provisions. One way to prevent wind up is to monitor the input speed frequency from the weighfeeder.
  • Page 78: Setpoint Controller - Rate Control

    (P201-02 = 4) speed optoinal remote setpoint - rate (P255-01 = 1) PID 1 process value source - load (P402-01 = 2) Page 72 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 79: Setpoint Controller - Master/Slave Control

    Setpoint Controller – Master/Slave Control belt scale motor speed controller load speed sensor control output rate (P201-02 = 4) SLAVE remote ratio speed setpoint rate (P255-01 = 1 PID 1 process value source - rate (P402-01 = 1) P418-01 to suit) belt scale motor speed...
  • Page 80: Setpoint Controller - Rate And Load Control

    If set too high, the BW500 becomes less stable, and more susceptible to oscillations in the control output. • allowable input range: 0.000 to 2.000 • typical operating range: 0.300 to 0.600 • default value: 0.400 Page 74 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 81: Integral Control (Automatic Reset), I

    The control output cannot reach the setpoint using only the term. Since the term acts on the difference between the setpoint and process variable, a small difference between these two always exist and the difference is never zero. A small term can get the process very close to set point, but it would take a very long time.
  • Page 82: Derivative Control (Pre-Act Or Rate), D

    I and terms alone. This is done on a one time basis. • allowable input range: 0.000 to 1.000 • typical operating range: 0.250 to 0.550 • default value: 0.300 Page 76 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 83: Pid Setup And Tuning

    The PID control function of the BW500 can be configured to operate in several modes. • controller output: direct acting • feedback: rate, load, or external • control: local or remote (ratio) setpoint PID Setup and Tuning Proper tuning of the control PID terms is essential to system operation and optimum performance from the feeder.
  • Page 84 Restart the feeder (test weights or chains still applied) and feed rate setpoint entered. Again observe the oscillation of the control output. Compare results to the figures 4,5 and 6 below. Figure 4 SETPOINT I term is too high Page 78 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 85 Figure 5 SETPOINT I term is too low Figure 6 SETPOINT I term is correctly set term is not critical in typical shearing type weigh feeder applications. The purpose of the term is to anticipate where the process is heading by looking at the time, rate, and direction of change of the process variable.
  • Page 86: Programming

    5 and 6 on the mA I/O board. • mA input 2 is an external signal normally reserved for controller 2. The signal is input at terminals 7 and 8 on the mA I/O board. Page 80 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 87 select the appropriate range for the mA P250-01 mA Input Range input signal Select 1- 0 to 20, 2-4 to 20 assign either: P255-01 mA Input Function 1: PID setpoint, or Select: 0, 1-PID SP, 2-PID PV 2: process variable as the function of the mA input enter the value, e.g.
  • Page 88 Select 0, 1-PID SP, 2-PID PV 2: process variable as the function of the mA input The PID setpoint can be modified while in RUN mode using the up/down Note: arrow keys. Page 82 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 89: Batching

    Batching The batching process, as it relates to the BW500 operation, can be defined as the transfer of a predetermined quantity of material. The process supports a count up operation (P560), in that the total (totalizer 5) begins at zero and increments up to the programmed setpoint (P564). A relay (RL1 through 5) programmed as the batch setpoint function (P100 = 8) is actuated when the material total reaches the setpoint.
  • Page 90: Connections

    P567, batch pre-warn setpoint Access P568 Batch Pre-act set to OFF (0) or AUTO (1) or manual (2) Relays select relay (1 – 5) Access P100, Relay Function select function 7, Pre-Warn Page 84 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 91: Operation

    Operation Once the BW500 relays are connected to the process logic, and it is programmed, the BW500 is ready for totalizing the batch and stopping the process when the batch setpoint is reached. The batch operation: start, pause, resume, and cancel are controlled externally by the process control (e.g.
  • Page 92: Communications

    The BW500 and BW500/L supports two protocols: Dolphin and Modbus. Dolphin is a proprietary Siemens Milltronics protocol designed to be used with Dolphin Plus. Modbus is an industry standard protocol used by popular SCADA and HMI systems.
  • Page 93: Bw500 And Bw500/L And Smartlinx

    BW500 and BW500/L and SmartLinx® In addition to three onboard communication ports, the BW500 and BW500/L is compatible with Siemens’ SmartLinx® communication modules which provide an interface to popular industrial communication systems. This section only describes the onboard communications. For more information on SmartLinx®, please consult the appropriate SmartLinx®...
  • Page 94: Configuring Communication Ports

    Modbus standard in both ASCII and RTU formats. It also supports direct connection of a printer. The Siemens protocol is compatible with the Dolphin Plus configuration program. See the Siemens web site for information on this PC product (http://www.siemens.com/processautomation).
  • Page 95: P771 Protocol Address

    The unique identifier of the BW500 and BW500/L on the network for the selected port, ports 1 to 3 (P771-01 to -03). For devices connected with the Siemens Milltronics protocol this parameter is ignored. For devices connected with a serial Modbus protocol this parameter is a number from 1- 247.
  • Page 96: P774 Data Bits

    BW500 and BW500/L. See your modem documentation for information on fixing the baud rate. Values no modem connected modem connected Page 90 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 97: P779 Modem Idle Time

    P779 Modem idle time Sets the time in seconds that the BW500 and BW500/L will keep the modem connected even though no activity is happening. To use this parameter ensure that P778=1. This parameter allows for reconnection to the BW500 and BW500/L unit after an unexpected disconnect.
  • Page 98: P781 Data Message

    SmartLinx® card to the BW500 and BW500/L, set P799 = 1 and not write anything to the SmarLinx® card, your setpoints will be 0. Totalizer 1 and/or 2 as set by P647, Totalizer Display. Not available with BW500/L Page 92 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 99: Dolphin Protocol

    The protocol is available on all communications ports on all units. This protocol is not available for third party use. The primary use of this protocol is to connect the BW500 and BW500/L to Siemens Milltronics’ Dolphin Plus configuration software.
  • Page 100: Modbus Rtu/Ascii Protocol

    At the time of publication of this manual, the Modbus Protocol was located under products / technical publications / communications products / Modbus protocol. Siemens does not own the Modbus RTU protocol. All information regarding Note: that protocol is subject to change without notice.
  • Page 101: Modbus Rtu Vs. Ascii

    Modbus RTU vs. ASCII There are two main differences between Modbus RTU and Modbus ASCII. The first is that Modbus RTU encodes the message in 8-bit binary, while ASCII encodes the message in ASCII characters. Therefore, one byte of information would be encoded into 8 bits for RTU and into two ASCII characters for ASCII (which would be two 7-bit units).
  • Page 102 41,003 00 - 23 see P009 41,004 00 - 59 page 113 and Time page 100 41,005 00 - 59 see P739 Time Zone 41,006 -12 - 12 page 143 Page 96 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 103 Parameter Type Description Start Read Reference Values Rate 41,010 32 bits Load 41,012 32 bits Speed 41,014 32 bits see page 101 Total 1 41,016 32 bits Total 2 41,018 32 bits Device State 41,020 bit mapped see page 101 Command Control 41,022 bit mapped...
  • Page 104: Modbus Register Map (Cont' D )

    Parameter on page 143. Device Identifier (R40,064) This value identifies the Siemens Milltronics device type and is “2” for the BW500 and BW500/L. Handshaking Area (Parameter Access) Built into BW500 and BW500/L is an advanced handshaking area that can be used to read and write 32 bit parameters.
  • Page 105 Writing Parameters To set parameters through Modbus follow these steps: Send the parameter, its primary index, and its secondary index (usually 0) to registers 40,090, 40,091, and 40,092. Write the value to registers 40,096 and 40,097 Write the desired format word to register 40,093 to enable the BW500 and BW500/L to interpret the value correctly.
  • Page 106 R41,001 R41,002 R41,003 R41,004 R41,005 R41,006 The time zone register is used only as a reference and does not affect the Note: operation of the BW500. Not available with BW500/L. Page 100 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 107 Process Values (R41,010 – R41,048) Rate, Load, Speed, and Total (R41,010 – R41,019) The associated registers provide the readings of rate, load, and speed. Totalizer 1 and Totalizer 2 in engineering units as displayed in the local BW500 and BW500/L display. Device State (41,020 –...
  • Page 108 Reset Batch Total- No change Reset izer Print Print Not available with BW500/L. WARNING: Before the BW500BW500 and BW500/L can be commanded remotely, parameter P799 must be set for remote control. Page 102 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 109 Read/Write (R41,025 – R41,026) Total Decimal Places Sets the number of decimal places (0-3) being read for Total 1, (words 41,016 and 41,017) and Total 2, (words 41,018 and 41,019). With 3 decimal places, the largest value that can be read is 2,147,483.648. With 2 decimal places, the largest value that can be read is 21,474,836.48.
  • Page 110 The standard BW500 provides only one mA output (0/4 – 20 mA). The inclusion of an optional mA I/O card provides two mA inputs (0/4 – 20 mA) and two additional mA outputs. The optional mA I/O card is not available with BW500/L Page 104 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 111 PID Tuning (R41,400 – 41,419) For BW500 set up for PID control, several registers have been provided for tuning. Refer PID Control on page 71 and the associated parameters as listed in the register map. Before you can change any of the setpoints, P799 must be set for remote Note: control.
  • Page 112: Text Messages

    Text Messages If a Siemens Milltronics device parameter returns a text message, that message is converted to a number and provided in the register. The numbers are shown in the table below: Number Text Message as Displayed on LCD 22222...
  • Page 113: Modems

    Modems The BW500 and BW500/L has been successfully connected to several different modems. In general, the Modbus protocol is a very modem friendly protocol. This section gives some general guidelines on modems and their connection. For detailed information, see the modem documentation. Picking Modems There are several different types of modems;...
  • Page 114 P778, port 1, to the value 1 (Communications through Modem) • set P779, port 1, to the value 300 (Modem Inactivity of 300 seconds) Parameters are defined the in the Installation section (page 9). Note: Page 108 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 115: Error Handling

    Error Handling Modbus Responses When polled by a Modbus Master, a slave device will do one of the following: Not reply means something went wrong with the transmission of the message Echo back the command with the correct response is the normal response, (see the Modbus specifications for more details) Return an Exception Code reflects an error in the message BW500 and BW500/L uses the following exception codes:...
  • Page 116 If the user attempts to write one or more registers that are out of range, an exception response code 2 will be generated. • If using an unsupported function code, undocumented results may occur. The user is encouraged not to do this. Page 110 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 117: Parameters

    Parameters indicates factory set value P000 Security Lock Locks out the program editor so that parameter values for P001 through P999 cannot be changed. This however, does not prevent the access to the parameters for viewing. Programming is locked out if the value of P000 is other than 1954. Entry: 1954 = unlocked 1954 = locked...
  • Page 118 P003 Number of Load Cells Siemens belt scales are available in models of one, two, four, or six load cell design. Select the number of load cells corresponding to the belt scale connected. If using the optional remote LVDT conditioner card, for LVDT based scales, select the “1”...
  • Page 119 P008 Date yyyy-mm-dd Enter the current date in format: yyyy = year mm=month, 01 –12 dd=day, 01 – 31 e.g. 1999-03-19 (March 19, 1999) P009 Time hh-mm-ss Enter the current time in 24 hour format. Where: hh=hour mm=minute ss=second P011 Design Rate Specifies the design rate of material flow for the belt scale ( = 0.00).
  • Page 120 P682. Example: 3 standard MSI test weights, 1.2 meter idler spacing Test Load = 24.6 kg (3x8.2 kg) = 20.5 kg/m 1.2 m Multispan function is not available with BW500/L. Page 114 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 121 P018 Speed Adjust This parameter allows adjustment to the speed constant for both speed sensors (P015-01 or P015-02) . Initially, this parameter displays the dynamic speed of the belt. If the displayed speed is not equal to the actual speed, enter the actual belt speed ( = 0.00).
  • Page 122: Relay/Alarm Function (P100 - P117)

    These parameters are specific to the use of the relay/alarm function. Refer to on page 63. Damping is not applicable to the mA output if programmed for PID function (P201 = 4). Page 116 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 123 P100 Relay Function Sets the relay function for the relay selected; BW500: relays 1 to 5 (P100 -01 to -05), BW500/L: relays 1 and 2 (P100 - 01, 02) Note: • To reset the Diagnostics relay, the BW500 and BW500/L must be cycled between PROGRAM and RUN mode •...
  • Page 124 Enter the value in % of full scale, or for deviation alarm enter % of setpoint, range is 1 to 10 %. Not applicable if P100 = 4, 7, or 8. Note: Not available with the BW500/L. Page 118 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 125: Ma I/O Parameters (P200 - P220)

    P118 Relay Logic Sets the logic applied to relays to determine their open or closed state. Power Failure The relays on the BW500 default to normally open under power loss. Normal Operation In software, all relays are programmed the same way; with ON setpoints always indicating relay action.
  • Page 126 Enter limit value, range 0 - 22 BW500/L has one output, parameters will not present multiple indexes. Not available with BW500/L. Valid for outputs 2 and 3, only if PID system (P400) is enabled. Page 120 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 127 P214 4 mA Output Trim Trims the 4 mA output level for the output selected, outputs 1 to 3 (P214 - 01 to – 03) . The trim adjust the output to agree with a milliameter or other external mA input device. Scroll the trim value up or down P215 20 mA Output Trim...
  • Page 128 PID function in the auto mode PID freeze: freeze function in the auto mode and holds output at last value remote PID setpoint source: local Not available with BW500/L. Page 122 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 129 Value Function Symbol Description auto PID mode: manual the input contacts status is external alarm: sensed off keypad / Dolphin Plus write (pro- remote gram) enabled communication SmartLinx®/ remote device write write: (program) enabled momentary closure of the input initiate online contact initiates online calibra- calibration: tion...
  • Page 130 1 and 2 selection. Input 2 is reserved for multispan 3 and 4 selection. Input 3 is reserved for multispan 5 to 8 selection. Not available with BW500/L Enter 1 (existing – ALT_DSP) to reject the new online calibration span. Page 124 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 131: Calibration Parameters (P295 - P360)

    If an attempt is made to select a multispan that has not been zero and span calibrated, the selection request is ignored. Note: • When performing a remote span, it will first perform a zero, then it will ask you to set up span test. Once loading is within 2% of the design test weight, it will perform the span.
  • Page 132: Online Calibration Options (P355 To P358)

    = 0%) P357.3 LOW LIMIT, range 0.0 to 100.0 ( = 0%) P358 Online Calibration Activation Initiates online calibration. Entry: 0 = OFF 1 = ON Not available with BW500/L. Page 126 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 133 P359 Factoring Factoring is used as a method of calculating the value of the test load (P017) to a new test reference; either: weight, or chain. The task is performed only for the weight or chain relevant for the multispan selected, if applicable. Entry: 1 = weight ( = 1)
  • Page 134 Note: P388 Initial Span Resets the initial span for the span selected, multispan 1 to 8 (P388-01 to -08) BW500/L has one span entry possible, no indices will be presented. Page 128 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 135: Linearization Parameters (P390 - P392)

    The initial span is the reference to which all subsequent span calibrations are compared in determining whether they have deviated beyond an accumulated 12.5% of the initial span ( = 1). Initial Span Refer to on page 49 for execution. Note: Linearization Parameters (P390 - P392) These parameters are used to compensate for non-linear response of the weighing...
  • Page 136: Proportional Integral Derivative (Pid) Control Parameters (P400 - P419)

    However in unstable or slow reacting systems the controller update can be programmed Not available with BW500/L. BW500/L does not have mA inputs, only a fixed incline compensation value can be entered. Not available with BW500/L. Page 130 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 137 to update on a multiple of the process value update. A high value can introduce instability = 1). Entry: 1 = 300 ms 2 = 600 ms 3 = 900 ms, etc. 7ML19985DK05Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS Page 131...
  • Page 138 When the PID system is in manual, this is the value output, providing bumpless transfer when switching from manual to auto. When switching from auto to manual, this parameter is loaded with the current controlled value. Page 132 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 139 P414 Setpoint Configuration Configures the setpoint (P414-01 or -02) for the corresponding PID system (1 or 2). Determines the source for the PID’s setpoint. If local, the setpoint value is entered into P415. The setpoint can be set from the mA input 1 or 2. The mA value is scaled to the full scale value of the process value (P402).
  • Page 140: Batch Control (P560 - P568)

    Sets the setpoint for the pre-warn function (P566). When the batch reaches the setpoint, the relay contact associated with the pre-warn function (P100) closes ( = 0.000). Enter setpoint in units of weight selected (P005). Not available with the BW500/L Page 134 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 141 P568 Batch Pre-Act Acts on the batch operation such that when the batch totalizer is reset, the batch total is compared to the setpoint (P564). The difference is then applied to pre-act on the setpoint for the next batch to improve the accuracy of the batch. The activity is internally limited to 10% of the batch setpoint.
  • Page 142: Totalization (P619 - P648)

    2 = 0.01 (one hundredth) 3 = 0.1 (one tenth) 4 = 1 (unit) 5 = 10 (x ten) 6 = 100 (x hundred) 7 = 1000 (x thousand) Not available with the BW500/L Page 136 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 143 P634 Communication Totalizer Resolution Used to set the number of fixed decimal places for Total 1 and Total 2 for SmartLinx or Modbus communication. Entry: # of decimal P634 Index Description Value places Primary Index 1 Total 1 for SmartLinx communication Primary Index 2 Total 2 for SmartLinx communication With 3 decimal places set, the largest readable value is 2, 147, 483.638.
  • Page 144 If the duration selected causes the totalizer to lag behind the count rate, the next possible duration is automatically entered. • External Totalizer output frequency must not exceed 13.33 Hz at 150% of design rate. Page 138 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 145 P647 Totalizer Display Selects the totalizer combination to be displayed, either manually through the scroll display key or automatically by control of the display mode (P081). Entry: 1 = totalizer 1 2 = totalizer 2 3 = totalizer 1 and 2 P648 Totalizer Reset, Internal Manual reset of the selected internal totalizer when the entry is made ( = 0).
  • Page 146 For speed constant entry (P690 = 2), this parameter is enabled for entry of the pulses per revolution that the speed sensor delivers (P692-01 or 02) Enter the pulses per revolution from the speed sensor nameplate. BW500/L has only one speed input Page 140 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 147: Ecal Parameters (P693 - P698)

    ECal Parameters (P693 – P698) Accessible only through P017 for ECal test reference. After Ecal completion, only a zero calibration is necessary to allow access to the RUN mode. P693 Load Cell Capacity Units Determines the units used for entering eCal data: 1 = kg 2 = lb 3 = Other (mV Span)
  • Page 148 Upon entry, display jumps to P017 to display the design load value as the test load. P735 Back Light Sets the intensity of the back light for the LCD ( = 10). Entry: 0 = off 1 to 10 = low to high Page 142 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 149: Communication (P740 - P799)

    P739 Time Zone The offset from Greenwich mean time (GMT) of local time. This parameter does not affect any timed events because all times are local. It can be accessed by a remote computer for synchronization purposes. Enter local time zone –12 to 12 Communication (P740 - P799) Changes to these parameters are not effected until the power to the unit is Note:...
  • Page 150 FAIL Error occurred communicating with card; device will try to reinitial- ize communications with card. If message continues, record values in P791 and P792 and contact your local Siemens representative. ERR1 No module installed, or module not supported; SmartLinx communi-...
  • Page 151: Test And Diagnostic (P900 - P951)

    Tests the memory. Test is initiated by scrolling to the parameter or repeated by 'pressing enter' Display: PASS = normal FAIL = consult Siemens. P911 mA Output Test Tests the mA output value for the output selected, outputs 1 to 3 (P911 -01 to -03) Displays the value from the previous measurement.
  • Page 152 Registers the number of zero calibrations that have been done since the last master reset = 0). Depending on the number of load cells selected by P003, not all load cells may be in use. Not available for BW500/L Page 146 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 153 P951 Span Register Registers the number of span calibrations for the span selected, span 1 to 8 (P951 - 01 to - 08), that have been done since the last master reset ( = 0). P952 Design Load Displays the value of the design load, which corresponds to the full scale value for alarm and mA output functions.
  • Page 154: Troubleshooting

    Specifically Q1: I tried to set a Siemens Milltronics device parameter, but the parameter remains unchanged. Try setting the parameter from the keypad. If it can’t be set using the...
  • Page 155: Error Codes

    Flashes in the bottom right corner of display when bat- tery charge is too low. Err: 227 No process data available. Consult Siemens. Batch pre-act adjustment Pre-act adjustment is ignored. Tune process to limit batch > 10% error.
  • Page 156: Certification

    Damping Display P081 Display scroll mode P400 - P419 P631 Lock index ’01’ , unlock remaining index ’02 - 05’ P634 Unlock P635 Unlock P647 Unlock Not available with BW500/L Page 150 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 157: Certification Printing

    Certification Printing Certification printing is allowed if the following conditions are met: • certification switch is set • rate is below 2 % • a communications port has been programmed for a printer The printout must consist of the following: Date: YYYY-MM-DD Time:...
  • Page 158: Glossary

    Usually the first zero performed, it is used as reference for all other zeros to determine whether they have deviated beyond the Zero Limit (P370). Input/Output Trim Allows the 4 and 20 mA values to be adjusted and verified with an external source (meter). Page 152 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 159 Linearization Compensates for non-linear output of the belt scale caused by varying load rates. Load Cell Strain Gauge type transducer that produces an electrical output proportional to force (load) applied. LVDT An electromechanical transducer that produces an electrical output proportional to the displacement of a separate movable core.
  • Page 160 An incremental counter that records the total of material that has been monitored. Zero Register Shows the number of zero calibrations that have been performed since the last master reset. Page 154 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 161: Memory Backup

    Refer to battery on page 27. Software Updates Software updates require Siemens Dolphin Plus software, contact your local Siemens representative. It is recommended that the old software and parameters be saved to your PC before downloading the new software.
  • Page 162: Appendix Ii: Software Revision History

    Auto Zero alarm relay will now reset toggling from program to run mode • Updated calibration error so that it will 2.06 February 17, 2001 not display a negative 0 error, -0.00% Page 156 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 163 Software Date Changes Revision • Added flowmeter option • Parameters are no longer changeable 3.00 April 27, 2001 with remote communications when certification switch set • Increased maximum idle time for SmartLinx to 9999 seconds • Fixed totalizer error when load is negative and totalizer drop out is 0.00 3.01 July 17, 2001...
  • Page 164 Word order format with remote communication fixed • Integrator serial number added to printout • Power failure message added to printout • Fixed word order for SmartLinx 3.12 August 2009 Page 158 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 165 Software Date Changes Revision • BW500/L option added • Updated eCal and test load parameters • Added option 11 to P100 • Zero and Span show progress in % • Added display and mA drop-out • Totalizer dropout (P619) now limited to •...
  • Page 166: Index

    74 I/O board 71 rate 71 input 67 system 74 output 6 controller output test 145 function 80 maximum separation 87 logic 69 Modbus 98 PID 77 protocol 86 Page 160 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 167 modbus P107 relay alarms 118 how modbus works 94 P117 relay dead band 67 responses 109 P118 relay logic 67 RTU/ASCII protocol 94 P119 relay override 119 modem 86 P200 mA output range 66 modems 107 P201 mA output function 66 available 90 P204 mA output average 120 example setup 108...
  • Page 168 P999 master reset 70 mV 142 parameters recalibration 46 read and write 98 remote 52 reading 98 routine 48 SmartLinx hardware testing 143 verification 137 values 105 stop bits 90 writing 99 Page 162 Milltronics BW500 and BW500/L - OPERATING INSTRUCTIONS 7ML19985DK05...
  • Page 169 term derivative 75 forward 132 integral 132 proportional 132 test load 42 material 42 value 145 text messages 106 totalizer 70 functions 68 internal 137 master 68 troubleshooting 148 UDINT 105 UINT32 order 98 unsigned double precision integer 105 web site 94 wiring 9-pin to RJ-11 25 guidelines 87...
  • Page 170 For more information www.siemens.com/level www.siemens.com/weighing Siemens AG Subject to change without prior notice Industry Sector 7ML19985DK05 Rev. 5.0 1954 Technology Drive 7ml19985DK05 P.O. Box 4225 © Siemens AG 2010 Peterborough, ON Canada K9J 7B1 Printed in Canada email: techpubs.smpi@siemens.com www.siemens.com/processautomation...

This manual is also suitable for:

Milltronics bw500/l

Table of Contents