DNP DEVICE PROFILE
Object 2 (binary input changes)
200
Qualifier codes for requests, object 1, variation 0:
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
There are no codes used for responses.
Object 1, Variation 1: Binary input
Object 1, Variation 2: Binary input with status
The following codes are used for requests.
Function codes for requests, object 1, variations 1 and 2:
1 (read)
22 (assign class)
Qualifier codes for requests, object 1, variations 1 and 2:
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
The following codes are used for responses.
Function codes for responses, object 1, variations 1 and 2:
129 (response)
Qualifier codes for responses, object 1, variations 1 and 2:
00, 01 (start-stop)
17, 28 (index)
Object 2, Variation 0: Binary input change
Variation 0 is used to request the default variation. The following codes are used for
requests.
Function codes for requests, object 2, variation 0:
1 (read)
Qualifier codes for requests, object 2, variation 0:
06 (no range, or all)
07, 08 (limited quantity)
There are no codes used for responses.
Object 2, Variation 1: Binary input change without time
Object 2, Variation 2: Binary input change with time
The following codes are used for requests.
Function codes for requests, object 2, variations 1 and 2:
1 (read)
Qualifier codes for requests, object 2, variations 1 and 2:
06 (no range, or all)
07, 08 (limited quantity)
The following codes are used for responses.
Function codes for responses, object 2, variations 1 and 2:
129 (response)
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – COMMUNICATIONS GUIDE
CHAPTER 3: DNP COMMUNICATION