3 Functions
By changing the setting of DIP2(2) switch, after the drive inverter has been
powered-down/powered-up, the parameters for the rated motor frequency P0310,
max. frequency P1082 and reference frequency P2000 are automatically pre-set.
In addition, the rated motor parameters as well as all of the other parameters which
depend on the rated motor parameters, are reset. The units of the power
parameters are, depending on P0100, are either interpreted as kW value or hp
value.
NOTE
Switch DIP2(1) (refer to Fig. 3-19) under the I/O board has no function.
3.5.2

Quick commissioning

If there is still no appropriate parameter set for the drive, then a quick
commissioning must be carried-out for the closed-loop Vector control and for the
V/f control including a motor data identification routine. The following operator units
can be used to carry-out quick commissioning:
BOP
AOP
PC Tools (with commissioning software STARTER, DriveMonitor)
When the quick commissioning is carried-out, the motor – drive inverter is basically
commissioned; the following data must be obtained, modified or entered before
quick commissioning is started:
Enter the line supply frequency
Enter the rating plate data
Command / setpoint sources
Min. / max. frequency or ramp-up / ramp-down time
Closed-loop control mode
Motor data identification
Parameterizing the drive with BOP or AOP
Parameters, designated with a * offer more setting possibilities than are actually
listed here. Refer to the parameter list for additional setting possibilities.
START
P0003 = 3
P0004 = 0
74
Factory setting: Bold
User access level *
1
Standard (basic applications)
2
Extended (standard applications)
3
Expert (for complex applications)
Parameter filter *
0
All parameters
2
Inverter
3
Motor
4
Speed sensor