MICROMASTER 440
Operating Instructions
6SE6400-5AW00-0BP0
The parameters are sub-divided into groups according to their functionality. This
increases the transparency and allows a parameter to be quickly searched for.
Furthermore, parameter P0004 can be used to control the ability to be visualized for
the BOP / AOP.
0
all parameters
2
drive inverter parameters
3
motor parameters
4
speed encoder
5
technical applications / units
control commands, digital I/O
8
Analog inputs/outputs
10
Setpoint channel and ramp-function gen. 1000 .... 1199
12
Drive inverter functions
13
Motor open-loop/closed-loop control
20
Communications
21
Faults, warnings, monitoring functions"
22
Technological controller (PID controller) 2200 .... 2399
Description for Binector Input (BI), Binector Output (BO), Connector Input (CI),
Connector Output (CO) and Connector Output / Binector Output (CO/BO), refer to
Section 3.1.2.3
Binector Input
Binector Output
Connector Input
Connector Output
Connector Output / Binector Output
Description for the command data set (CDS) and drive data set (DDS) refer to Section
3.1.3
Command data set
Drive data set
"P" parameters can only be changed depending on the drive state. The parameter
value is not accepted if the instantaneous state is not listed in the parameter attribute
"Change state". For instance, the commissioning (start-up) parameter P0010 with the
attribute "CT" can only be changed in quick start-up "C" or ready "T" but not in run
"U".
Quick commissioning (start-up)
Operation (run)
Ready
This parameter attribute identifies as to whether the parameter is included in the quick
commissioning (start-up) (P0010 = 1).
The parameter is not included in the quick commissioning (start-up)
The parameter is included in the quick commissioning (start-up)
This attribute is only of importance in conjunction with a BOP. The "Immediate"
attribute indicates that this value is already accepted when scrolling (when changing
the value with
or
). Especially parameters which are used for optimization
functions have this property (e.g. constant voltage boost P1310 or filter time
constants). On the other hand, for parameters with the attribute "After actuation", the
value is only accepted after first actuating the key
parameters where the parameter value can have different settings/meanings (e.g.
selecting the frequency setpoint source P1000).
The value becomes valid by either scrolling with
The value is only accepted by pressing
Description
Main parameter area:
0200 .... 0299
0300 .... 0399 and
0600 .... 0699
0400 .... 0499
0500 .... 0599
0700 .... 0749 and
0800 .... 0899
0750 .... 0799
1200 .... 1299
1300 .... 1799
2000 .... 2099
2100 .... 2199
. These include, for example,
or
3 Functions
51