Step 3: (Optional) Activate External Critical Alarm

The BSIA system is not equipped with an external critical alarm. If one was not
Note
purchased, skip this Step.
1. Connect pair 22 on connector block P1
to one input on the external alarm device
(see
Figure
18).
2. Connect tip (normally closed) or ring
(normally open) of pair 23 on P1 to the
other input of the alarm device.

Step 4: Determine Base Station Power Supply

A Base Station can receive input (line) power from the BSIA or an optional local power supply.
Using a local power supply increases the distance Base Stations can be located from the BSIA.
Toshiba provides an optional universal 110/230VAC, 50/60 Hz power supply with a barrel-jack
connection to the Base Station (see
Customers with 220VAC outlets can:
o
Purchase another power cord to fit the universal connector (three-pronged IEC 320 power
inlet) on the power supply.
o
Replace the 110VAC plug on the cable with an appropriate 220VAC plug.
o
Connect a North American 220VAC adapter to the 110VAC plug.
Strata AirLink Installation Guide
Figure 20
on
5/00
Step 3: (Optional) Activate External Critical Alarm
Lamp or Buzzer
Maximum Switched Power 60W
0.5 A, 125VAC Resistive
1.0 A, 48VDC Resistive
Pair 22 - Relay Common
Pair 23, Tip - Normally Closed Contact
Pair 23, Ring - Normally Open Contact
2981
Figure 18
Wiring for External Critical Alarm
Page
23).
BSIA System Installation
21