Further Settings For Analog Outputs - Siemens SINAMICS G150 Operating Manual

Converter cabinet units 75 kw to 800 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Output Terminals
8.4

Further Settings for Analog Outputs

Description
The customer terminal block (–A60) features two analog outputs for outputting
setpoints via current or voltage signals.
In addition to the settings described in Chapter 8.2, a function for scaling output
signals is available.
Signal Flow Diagram
AO Signal
p4071
Actual speed
r0063
Output current
r0068
DC-link voltage
r0070
...
Output power
r0082
Fig. 8-4
Signal flow diagram: Analog output 0
Additional Setting Parameters for Analog Output 0 (AO0)
Value x1 for the analog output
p4077[0]
characteristic
Setting for the x coordinate in % of the first point on the scaling characteristic.
Value y1 for the analog output
p4078[0]
characteristic
Setting for the y coordinate in V or mA of the first point on the scaling characteristic.
The unit is V when analog output 0 is set as a voltage output (p4076[0] = 1 / 4) and terminals X522: 1
and 2 are used.
The unit is mA when analog output 0 is set as a current output (p4076[0] = 0 / 2 / 3) and terminals X522:
3 and 2 are used.
8-8
Smoothing
act. V/I
p4073
r4074
Char. y2
p4080
x
Char. y1
Smoothing
p4078
Char. x1
Char. x2
p4077
p4079
y
[%]
y
2
y
x
x
x
2
1
y
1
Scaling
Setting range: -1000.00 ... +1000.00 %
Factory setting: 0.00 %
Setting range: -20.000 ... +20.000 V or mA
Factory setting: 0.000 mA
11/03
AO_type
Output
p4076
voltage
AO 0V+
X522.1
D
+-10V
X522.3
A
AO 0A+
+-20mA
Current output
AO 0 Bez
X522.2
SINAMICS G150
Operating Manual