p4076[0]
Analog output type
Setting parameter for the type of analog output 0 on the customer terminal block.
Values: 0: 0 ... 20 mA
1: 0 ... 10 V
2: 4 ... 20 mA
3: -20 ... +20 mA
4: -10 ... +10 V
Settings 0, 2, and 3: terminals X522: 3 and 2 must be used.
Settings 1 and 4: terminals X522: 1 and 2 must be used.
Setting Parameters for Analog Output 1 (AO1)
p4071[1]
Signal source for the analog output
Setting parameter for the signal to be output for analog output 1 on the customer terminal block.
p4073[1]
Smoothing time for analog output
Setting parameter for the time constant of the 1
r4074[1]
Current output voltage/current
The current output voltage is displayed in V when analog output 1 is set as a voltage output (p4076 = 1 /
4) and terminals X522: 4 and 5 are used.
The current output current is displayed in mA when analog output 1 is set as a current output (p4076 = 0
/ 2 /3) and terminals X522: 6 and 5 are used.
p4076[1]
Analog output type
Setting parameter for the type of analog output 1 on the customer terminal block.
Values: 0: 0 ... 20 mA
1: 0 ... 10 V
2: 4 ... 20 mA
3: -20 ... +20 mA
4: -10 ... +10 V
Settings 0, 2, and 3: terminals X522: 6 and 5 must be used.
Settings 1 and 4: terminals X522: 4 and 5 must be used.
SINAMICS G150
Operating Manual
Setting range: 0 / 1 / 2 / 3 / 4
Factory setting: 0: 0 ... 20 mA
Setting range: see list
Factory setting: r0068 (I_ACT)
Setting range: 0 ... 1000 ms
Factory setting: 0 ms
st
order low-pass filter for analog output 1.
Unit: V or mA
Setting range: 0 / 1 / 2 / 3 / 4
Factory setting: 0: 0 ... 20 mA
Output Terminals
8-3