<Installer Setting Code Table>
1) General air-conditioner product
Code
Function
01
Test Run
02
Address Setting
03
E.S.P. Value
04
Thermistor
05
Ceiling Height
06
Static Pressure
07
Master Setting
08
Override Setting
09
Dry Contact
Celsius Fahrenheit
12
Switching
Emergency
18
Heater Setting
20
Plasma
21
Electric heater
22
Humidifier
23
Elevation Grill
24
Ventilation Kit
25
Auxiliary Heater
Setting temperature
31
range
C Some contents may not be displayed depending on the product function.
01:Set
00~FF : Address
<ESP Step>
<ESP Value>
01:VeryLow
0 ~ 255
02:Low
03:Med
04:High
05:Very High
01:Remo
02:Indoor
03:2TH
01:Low
02:Med
03:High
04:Very High
01:V-H
02:F-H
03:V-L
04:F-L
00:Slave ※ If only "Plus1" series models 00 : Group setting
01:Master
00:Slave
01:Master
00:Auto-Off
01:Auto-On
00:Celsius
01:Fahrenheit
Select mode
Setup Low Ambient
Heating Operation
00 : not use
0 : not use
01 : use
1 : use – compressor off
(0 °F/-18 °C)/on(5 °F/-15 °C)
2 : use – compressor off
(5 °F/-15 °C)/on(10 °F/-12 °C)
3 : use – compressor off
(10 °F/-12 °C)/on(15 °F/-9 °C)
00: Not Installed
01: Installed
00: 60~86 °F / 16~30 °C
01: 40~99 °F / 4~37.5 °C
INSTALLATION INSTRUCTION
Value
<Example>
Function Code
ESP step
01 : Single setting
Setup FAN
Speed
0 : fan off
1 : fan on