1.2

Pre-installation Checklist

WARNING!
This installation must be made by a qualified service person and must conform to all local
codes.
WARNING!
CSA Certified / UL Listed CLASS 2 power adaptors or Certified PoE+ rated 42.5 VDC to
57 VDC, 600 mA, 34.20 W (max) power adaptor must be used in order to comply with
electrical safety standards.
1.
2.
WARNING!
Power and I/O cabling must be routed separately inside different permanently earthed metal
conduits.
3.
WARNING!
Install external interconnecting cables in accordance with NEC, ANSI/NFPA70 (for US
application) and Canadian Electrical Code, Part I, CSA C22.1 (for CAN application) and in
accordance with local country codes for all other countries.
CSA Certified / UL Listed CLASS 2 power adaptors must be used in order to comply with
electrical safety standards.
Branch circuit protection incorporating a 20 A, 2-pole Listed Circuit Breaker or Branch Rated
Fuses are required as part of the building installation. A readily-accessible 2-pole disconnect
device with a contact separation of at least 3 mm must be incorporated.
4.
CAUTION!
Select a rigid mounting location to prevent excessive vibration to the camera.
Bosch Security Systems, Inc.
Determine the location and distance for the junction box based on its voltage and current
consumption.
See Section 3 Connection, page 9, for wiring information and distances.
Use only UL-listed liquid tight strain reliefs for conduits to the junction box to ensure that
water cannot enter the box. You must use 3/4 in. (20 mm) NPS watertight conduits and
fittings (to meet NEMA 4X standards).
Route all rough wiring including: power, control, video coax, alarms I/O, relay I/O, and
fiber optic cabling. See Section 3 Connection, page 9, for video and control protocol
methods.
Select the appropriate mounting kit to use, depending on the location of the VEI-30 / NEI-
30 Series camera. The camera is intended to be mounted securely to a wall using the
mounting holes in the junction box.