When this tone sounds, evacuate all
occupants and investigate for smoke or fire.
The keypad display shows only the point text of the first
point that entered fire alarm. Press [NEXT] or [PREV] to
acknowledge this alarm or any other alarm condition or other
condition that is not normal. The first pressing of the [NEXT]
key performs an acknowledge function. Refer to Section 3.0
Keypad Navigation Keys on page 12.
Subsequent pressing of the [NEXT] key after the
acknowledge function shows any additional points that
entered alarm. Use the [NEXT] and [PREV] keys to show
events from the oldest to the newest and the highest to the
lowest priority.
Bosch Security Systems, Inc. | 8/06 | F01U011793B
Fire System | User's Guide | 4.0
4.3
Fire Troubles
After an alarm silences, the device that caused the alarm is
usually still faulted or activated. Press [DETECTOR RESET]
to reset a smoke detector. Refer to Section 11.1.2 DETECTOR
RESET ? on page 25. A device in a state that is not normal
creates a fire trouble condition.
Examples of trouble conditions include such things as a
broken wire. When a fire trouble occurs, your keypad
repeatedly emits a series of three warble tones followed by a
pause.
The system shows the number of fire points with troubles
(A1 ## FIRE TRBLE) in an area and then shows the
custom text for the highest priority trouble condition. Use the
[NEXT] and [PREV] keys to view the other trouble
conditions.
System Events
14