Toshiba AD268 User Manual page 67

Programmable controller prosec t2-series analog i/o modules
Table of Contents

Advertisement

PART 3 TC218
3.2 Parameter setting by software
The input type of the TC218 is specified by writing the following parameter data into the
TC218's buffer memory. To access the buffer memory, T2 user program (READ and WRITE
instructions) is required.
When the parameter is set to the TC218, it is saved in the TC218's built-in EEPROM.
Therefore, once the input type parameter is set, there is no need to execute the input type
setting operation.
Input type parameter data:
Parameter
data
TC218 buffer memory address:
H8018
H8019
H801A
H801B
H801C
H801D
H801E
H801F
Set the same parameter data for all 8 channels.
The factory setting is
For details of the procedure to set the input type parameter, refer to section 6.
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
T2 CPU
User program
Input type
0
Type K thermocouple
1
Type J thermocouple
2
Type E thermocouple
5
100mV
Input type for channel 1
Input type for channel 2
Input type for channel 3
Input type for channel 4
Input type for channel 5
Input type for channel 6
Input type for channel 7
Input type for channel 8
100mV range.
Buffer memory
WRITE
READ
3. Input Type Setting