Parameter Setting Procedure - Toshiba AD268 User Manual

Programmable controller prosec t2-series analog i/o modules
Table of Contents

Advertisement

6. Parameters

6.2 Parameter setting procedure

When you change the AD268 parameters, such as input type settings, gain/offset calibrations
and averaging times, use the following procedure.
Step (1)
Write the value "0" into the command register of the AD268 buffer memory (address H8020)
by WRITE instruction.
H8020
Step (2)
Write the parameter data into the buffer memory (addresses H8000 to H801F) by WRITE
instruction. Be sure to write all the 32 words in batch.
H8000
H8001
:
H801F
Step (3)
Write the value "1" into the command register (address H8020) by WRITE instruction.
H8020
Step (4)
Wait until the data of the response register (address H8021) comes "1". Check the data by
READ instruction.
H8021
Step (5)
Write the value "0" into the command register (address H8020) by WRITE instruction.
H8020
When the above steps are finished and the module status (addresses H8030 to H8037) shows
no error, the parameter setting procedure is completed. The parameters are effective and they
have been saved in the AD268's EEPROM.
30
Analog I/O Modules (AD268 / DA264 / TC218)
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Command register
Gain for channel 1
Gain for channel 2
:
Input type for channel 8
Command register
Response register
Command register
Write 0
Write the parameter data (32 words)
Write 1
Check if it comes 1
Write 0
PART 1 AD268

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tc218Da264

Table of Contents