Toshiba AD268 User Manual page 30

Programmable controller prosec t2-series analog i/o modules
Table of Contents

Advertisement

6. Parameters
Command register:
(H8020)
This register is used to issue the following commands to the AD268. To issue the command,
write the command value by using WRITE instruction.
Value
The command register and the response register are used for hand-shaking. Refer to section
6.2 for the parameter setting procedure.
Response register:
(H8021)
This register shows the AD268's response for the command issued. Check the status of this
register using READ instruction.
Value
The command register and the response register are used for hand-shaking. Refer to section
6.2 for the parameter setting procedure.
28
Analog I/O Modules (AD268 / DA264 / TC218)
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Command
0
-
1
Parameter set
2
Reset command
Response
0
-
1
Acknowledge
Write 0 after the command processing is completed.
When this command is issued, the parameters written into
the buffer memory are saved in the AD268 's EEPROM, and
the parameters become effective.
Used to reset the AD268 when some error has occurred.
However if the error is caused by hardware or external
condition, the reset command may not be effective.
The requested command is not yet completed.
When the issued command is completed, the response
register comes 1.