Advertisement

ANCB/DN Specifications,

Cable Types

Cable Type
Fiber Optic
MM 62.5/125; 2 Fiber Conductors
2- Conductor Copper Wire
4-Conductor Copper Wire
Ethernet Cat 5 Unshielded Twisted
pair (UTP)
4 • Installation
Continued
The following Table should be used when evaluating or selecting cable
for an existing or new installation.
Vendors & P/N
SEA P/N 1270002-002
Industry Available from
Multiple Vendors
SEA P/N 1686002-001
Belden P/N 9182
Belden Armored Cable
SEA P/N 1680000-002
SEA P/N 1681000-003
Belden P/N SSD1743
SEA P/N 1681003-006
Industry Available from
Multiple Vendors
Installation Notes
New Installation as an
alternative to copper cable
Max distance from Analyzer
to Hub or between Hubs
1520 meters (5000 ft)
Recommended for Single
Channel
Max distance from Analyzer
For
to Hub or between Hubs
1520 meters (5000 ft)
Order
Recommended for Dual
Channel
Max distance from Analyzer
to Hub or between Hubs
1520 meters (5000 ft)
Recommended for short
distances or within shelters.
Max distance from analyzer
to hub or between hubs 600
meters (2000 ft)