When scrolling the message "Please Wait....." might be shown for "a second" and "No more sensors
found in the system" (before lowest and after highest possible number respectively).
Rev: 3
Sensor: 01-03 (technical address 003)
Momentary: XX°C
Sensor: 01-03
Current algorithm: nnnnnn
Start Sensor : 00-00
Sensor values
Perf. Factor = Performance factor:
Low (min. 0) = The detector is mounted in a "stable" environment.
High (max. 2.55) = The detector is mounted in an "unstable" environment.
See also Planning Instructions, chapter "Performance factor".
Table showing the algorithms and the shortenings respectively:
Normal sensitivity & Normal detection (15 s)
High sensitivity & Normal detection (15 s)
Low sensitivity & Normal detection (15 s)
Normal sensitivity & Slow detection (35 s)
High sensitivity & Slow detection (35 s)
Low sensitivity & Slow detection (35 s)
Heat algorithm, Class A1
Heat algorithm, Class A2 (S)
Heat algorithm, Class B (S)
Decision algorithm
Default is N-15 and A1 respectively.
83
If some other short name is wanted, it can be changed in Win128. Up to
six characters can be used. In the DBI (Danish) convention, up to five
characters.
84
Low sensitivity and/or slow detection (35 s) might not fulfil the EN54-7
specifications.
85
Analog multi detector 4300 only.
EBL128 Operating Instructions V1.1.x
Min: XX°C
Max: XX°C
ACCEPT?
Algorithm
98
Write the presentation
number and/or press "A"
to accept or press
"Return" to menu U3.
Scroll or press "Return"
U3
to menu H4. Scroll or
press "Return" to log off.
Short name
83
(nnnnnn)
N-15
H-15
84
L-15
84
N-35
84
H-35
84
L-35
A1
A2
B
85
Dec