Motor and brake connection

Table 6- 47
X1 Motor connection
For ring cable lugs without insulation
1)
Table 6- 48
X11 brake connector
The circuit for protecting the brake against overvoltage is integrated in the Motor Module and does not need to be installed
externally. The max. load current is 2 A, the min. load current 0.1 A.
WARNING
Danger to life as a result of a hazardous voltage at the 0 V to 48 V DC terminals
Death or serious injury can result when live parts are touched in the event of a fault.
• Only connect protective extra-low voltages (PELV / SELV) to all connections and
terminals between 0 to 48 V DC.
474
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Terminal
Technical data
U2
Threaded bolts M8 / 13 Nm
(refer to Chapter Connection systems (Page 731))
V2
W2
- (BR-)
PE connection
Threaded hole M8 / 13 Nm
Terminal
Technical data
+ (BR+)
Voltage 24 V DC
Max. load current 2 A
- (BR-)
Min. load current 0.1 A
Type: Spring-loaded terminal 2 (Page 754)
Max. cross-section that can be connected 2.5 mm
The brake connector is part of the prefabricated cable.
1)
1)
2
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
: