Siemens 6SL3120-2TE21-0AA3 Manual page 196

Booksize power units
Table of Contents

Advertisement

External air cooling
Rated power
DC link voltage
Overvoltage trip
Undervoltage trip
2)
Input currents
Rated input current
at AC 400 V:
Input current
at AC 380 V / AC 480 V
at AC 400 V; S6 - 40 %
at AC 400 V; peak current
DC link currents
Rated DC link current
at 600 V:
DC link current:
for 600 V DC; for S6 - 40 %
for 600 V DC; peak current
Current carrying capacity
DC link busbar:
24 V busbar:
Electronics current drawn
at 24 V DC
Total power loss
(including electronics losses, see
Power loss tables (Page 781))
Max. ambient temperature
without derating
with derating
DC link capacitance
Active Line Module
Drive line-up, max.
Power factor
Circuit breaker
(IEC 60947 and UL)
Rated short-circuit current
SCCR
3)
Sound pressure level
Cooling air requirement
Max. permissible heat sink
temperature
Weight
The specified power ratings apply to the line voltage range from 380 V to 480 V.
1)
Default for 400 V line systems; undervoltage trip threshold is adjusted to the parameterized rated voltage
2)
The resulting rated short-circuit current is obtained from the combination of the fuse or circuit breaker – and the Line
3)
Module in the drive system.
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
6SL3131–
7TE28–0AAx
kW
80
V
510 ... 720
DC
V
820 ± 2 %
DC
V
360 ± 2 %
DC
A
122
AC
A
128 / 102
AC
A
161
AC
A
200
AC
A
134
DC
A
176
DC
A
218
DC
A
200
DC
A
20
DC
A
1.4
DC
W
1383.6
° C
40
° C
55
μF
2820
μF
20000
cosϕ
1
See Section Overcurrent protection using line fuses and circuit
breakers (Page 51)
kA
65
dB(A)
< 73
m
/h
520
3
73
Rated voltage for rated data 3 AC 380 V
kg
27.66
4.3 Active Line Modules with external air cooling
7TE31-2AAx
120
182
192 / 152
220
267
200
244
292
200
20
1.8
2243.2
40
55
3995
20000
1
65
< 73
520
83
30.74
Line Modules Booksize