Honeywell MPA2C3 User Manual page 45

Access control unit
Hide thumbs Also See for MPA2C3:
Table of Contents

Advertisement

Note: A PIN ending in 0 (for example, 2320) will only trip a duress output when a 1 is used
in place of the 0 (for example, 2321).
Note: The duress output feature requires the following configurations:
Note: Duress must be enabled on the Panel Configuration > Settings > Behaviour Settings
tab. See figure 2-10 on page 30.
Note: A schedule/schedule must be selected for Card and PIN in the Doors configuration.
Configuring Schedules
The MPA2C3 panel controls access by using schedules, or time schedules. Inputs,
outputs, groups, readers, access groups, and cards through access groups are all
configured with schedules by which they will be energized or de-energized,
enabled or disabled.
MPA2C3 User Manual
Anti -Passback-When enabled, a valid card is required for entry and exit.The
card holder must use the card in the proper IN/OUT sequence-that is, a card
presented at an IN reader must then be presented at an OUT reader, or vice
versa.
Free Egress–Configures the panel for free egress. When enabled (Default), the
panel automatically configures inputs REX1-4 to act as egress inputs for Doors
1 to 4, respectively. If disabled, those inputs REX1-4 can be used as general
inputs.
A duress PIN is the PIN a user enters at a keypad when being forced (for example,
during a robbery) to open a door. The card holder enters a PIN that is either one
number higher or lower than the correct PIN. This PIN opens the door, but it also
triggers the designated duress output and produces an alarm event.
For example, if the PIN is 2222, entering either 2221 or 2223 opens the door, but
triggers a duress pulse and generates an alarm. In this way, the card holder
notifies others without detection by the unauthorized person.
Continuous Card Reads – Enables continuous card reading while the output is
being energized. t caused by the previous card read. This parameter is set to
Enabled by default.
Password Expiration – When enabled, password expiration will be based on the
last time a user's password was updated. The password is good for 180 days.
When disabled, the system does not check for password expiration. This is not
recommended. Enabled by default. After 180 days when a user logs in, then the
system will prompt you to change the password.
Reverse LED Color – Identifies the color of a reader LED when a grant is
authorized. When this parameter is enabled, the LED should be solid red and
then turn green after two seconds (by default). Enabled by default. Web Session
Timeout– Activates a web session timeout after the specified time period has
elapsed. Define the time period either in minutes or in hours. Enter the number
in the box, then select either minutes (3-59) or hours (1-12).
45