How To Set Up The Cooling Only Indoor Unit - Toshiba MMY-MAP0806FT8P-E Installation Manual

Air conditioner (multi type)
Hide thumbs Also See for MMY-MAP0806FT8P-E:
Table of Contents

Advertisement

<In case of connecting one group operation of
indoor units and two indoor units>
Single port type FS unit
Piping
Indoor unit
Control wiring
Remote
between indoor unit
controller
and FS unit
(Within 15 m)
Group control
[ 0E ] :
1
1
0
[ 14 ] :
1
2
0
[ FE ] :
1
1
1
[ FD ] :
0
0
0
Multi port type FS unit (*1)
Piping
Indoor unit
Remote
controller
Group control
[ 0E ] :
1
1
0
[ 14 ] :
1
2
0
[ FE ] :
1
1
1
[ FD ] :
0
0
0
<In case of connecting four indoor units>
Single port type FS unit
Piping
Indoor unit
Control wiring
between indoor unit
and FS unit
Remote controller
(Within 15 m)
[ 0E ] :
0
0
0
[ 14 ] :
0
0
0
[ FE ] :
1
1
1
[ FD ] :
0
0
0
Multi port type FS unit (*1)
Piping
Indoor unit
Remote controller
[ 0E ] :
0
0
0
[ 14 ] :
0
0
0
[ FE ] :
1
1
1
[ FD ] :
0
0
0
59-EN
<Incorrect connection examples>
Incorrect
Single port type FS unit
Single port type
FS unit
Piping
Control wiring
Remote controller
between indoor unit
0
and FS unit
0
(Within 15 m)
Group control
1
0
Incorrect
Multi port type FS unit (*1)
Piping
Remote controller
0
Group control
0
Incorrect
1
0
Multi port type FS unit (*1)
Piping
Indoor
unit
Remote controller
0
0
Group control
1
Incorrect
0
Multi port type FS unit (*1)
Piping
Remote controller
Group control
0
0
1
0
9

How to set up the cooling only indoor unit

When setting the specific indoor unit to Cooling Only
unit without connecting to the flow selector unit, setup
to the indoor unit to become the Cooling Only unit is
necessary. Perform setup in the following procedure.
Setup to the indoor unit is performed by handling the
Indoor unit
wired remote controller.
Even if a wired remote controller is not used, attach a
wired remote controller for setup.
Change the setup with the wired remote controller
before using the air conditioner with a wireless remote
controller.
Change the setup during stop of the operation.
Single port type FS unit
(Be sure to stop operation of the air conditioner.)
Indoor unit
4
1
6
Multi port type FS unit (*1)
1
When pushing
simultaneously for 4 seconds or more,
after a while, the display part flashes as
shown in the figure.
Check that the displayed CODE No. is [10].
If the CODE No. indicates one other than [10],
push
retry the operation from the first step.
(After pushing
remote controller cannot be accepted after a
while.)
Indoor
unit
(* The display changes according to the indoor unit
model.)
– 30 –
2
In a group control, the firstly displayed
indoor UNIT No. becomes the header unit.
Every pushing
button), the indoor UNIT No. in the group control
is displayed successively.
In this time, the position of the indoor unit of
which setup is to be changed can be confirmed
SET
DATA
SETTING
because the fan and louver of the selected
indoor unit work.
No.
3
3
Use
temperature to specify the CODE No. [0F].
4
Use
select the setup data [0001].
5
2
5
Push
+
+
buttons
changes from flashing to lighting, the
setup completes.
button to erase the display, and then
button, the operation of
CAUTION
CODE No.
SET
DATA
SETTING
SETTING
Cooling Only and Heat pump cannot exist in the
UNIT No.
same group.
R.C.
No.
button (left side of the
Select an indoor unit of which
setting is to be changed.
CODE No.
SET
DATA
SETTING
SETTING
UNIT No.
R.C.
No.
and
buttons of the set
and
buttons of the timer time to
SET DATA
0000
0001
Cooling Only
Heat pump
Cooling Only
setup
button. In this time, if the display
To change the setup of an indoor unit other
than the selected one, start operation from
2
Procedure
.
In a group control, setup change of all the
indoor units in a group is necessary.
To change the setup of the set other than
the selected one, start again operation from
2
Procedure
.
Pushing
button clears the set up contents
which have been already set.
2
In this case, retry from Procedure
.
60-EN
EN