How to set up CODE No. [ 14 ]
It is necessary to set up group address in case of the
group control.
0 : Individual
1 : Header unit
2 : Follower unit
How to set up CODE No. [ FE ]
In cases other than connecting with one indoor unit or
one group in one branching, it is necessary to set up.
As for both single port type and multi port type, set
up CODE No. "FE" in one branching within the range
of 1~64.
This CODE No. should not be duplicate in one
system.
How to set up CODE No. [ FD ]
In cases other than connecting with one indoor unit or
one group in one branching, it is necessary to set up.
0 : Heating prioritized (Factory default)
1 : Cooling prioritized
In case of FE/FD without setting
Single port type FS unit
Piping
Indoor unit
Control wiring
between indoor unit
Remote controller
and FS unit
(Within 15 m)
Group control
Multi port type FS unit (*1)
Piping
Indoor unit
Remote controller
Group control
57-EN
In case of FE/FD with setting
Single port type FS unit
Piping
Indoor unit
Control wiring
Remote controller
between indoor unit
and FS unit
(Within 15 m)
Group control
Group control
Multi port type FS unit (*1)
Piping
Indoor unit
Remote
controller
Group control
Group control
Single port type FS unit
Piping
Indoor unit
Control wiring
between indoor unit
Remote
and FS unit
controller
(Within 15 m)
Group control
Multi port type FS unit (*1)
Piping
Indoor unit
Remote
controller
Group control
– 29 –
[ Set up example ]
[ 0E ] : Group setting
0 : Individual (Factory default)
1 : Group
[ 14 ] :
Group address
0 : Individual
1 : Header unit
2 : Follower unit
[ FE ] : Branching system address (1~64)
Should not be duplicate in one system
Factory default : 99
[ FD ] : Priority operation mode
0 : Heating prioritized (Factory default)
1 : Cooling prioritized (The cooling is
prioritized even if setting only one unit in
one branching)
< In case of connecting one indoor unit>
Single port type FS unit
Piping
Control wiring
between indoor unit
and FS unit
(Within 15 m)
[ 0E ] : It is not necessary to set up
[ 14 ] : It is not necessary to set up
[ FE ] : It is not necessary to set up
[ FD ] : It is not necessary to set up
Multi port type FS unit (*1)
Piping
[ 0E ] : It is not necessary to set up
[ 14 ] : It is not necessary to set up
[ FE ] : It is not necessary to set up
[ FD ] : It is not necessary to set up
<In case of connecting one group operation of
indoor units>
Single port type FS unit
Piping
Control wiring
between indoor unit
Remote controller
and FS unit
(Within 15 m)
Group control
[ 0E ] :
1
[ 14 ] :
1
[ FE ] :
It is not necessary to set up
[ FD ] :
It is not necessary to set up
Multi port type FS unit (*1)
Piping
Remote controller
Group control
Indoor unit
[ 0E ] :
1
[ 14 ] :
1
[ FE ] :
It is not necessary to set up
Remote
[ FD ] :
It is not necessary to set up
controller
<In case of connecting two group operations of
indoor units>
Single port type FS unit
Piping
Control wiring
Remote
between indoor unit
controller
and FS unit
Group control
Group control
(Within 15 m)
[ 0E ] :
1
1
[ 14 ] :
1
2
[ FE ] :
1
1
Indoor unit
[ FD ] :
0
0
Multi port type FS unit (*1)
Remote
controller
Piping
Remote
controller
Group control
[ 0E ] :
1
[ 14 ] :
1
[ FE ] :
1
[ FD ] :
0
Indoor unit
1
1
2
2
Indoor unit
1
1
2
2
Indoor unit
1
1
1
2
1
1
0
0
Indoor unit
Group control
1
1
1
2
1
2
1
1
1
0
0
0