Full opening of the valve
Open the valves of the outdoor unit fully.
MAP080
MAP100
Packed valve
Balance pipe
Using a 4 mm-hexagonal wrench, fully open the valve shaft.
Ø12.7 packed valve
Using a 4 mm-hexagonal wrench, fully open the
valve shaft.
Liquid side
Ball valve
Using a athead screwdriver, turn it counterclockwise by 90° until it hits the stopper. (Full open)
Service port
Discharge gas
side
(1)
(2)
Ball valve
Using a wrench, turn the valve shaft counterclockwise by 90° until it hits the stopper. (Full open)
Suction gas side
31-EN
MAP120
MAP140
MAP160
MAP180
MAP200
Ø15.9 packed valve
Using a 5 mm-hexagonal wrench, fully open the
valve shaft.
Position of screwdriver slot
Fully closed
Fully opened
Valve unit
Using athead screwdriver, turn
it counterclockwise by 90° until
it hits the stopper. (Full open)
Slot
* When opened fully, do not apply excessive
Flare nut
torque after the screwdriver hits the
stopper; otherwise a problem may be
caused on the valve. (5 N•m or less)
Fully closed
F-GAS label
This product contains uorinated greenhouse gases
• Chemical Name of Gas
• Global Warming Potential (GWP) of Gas
CAUTION
1. Stick the enclosed refrigerant label adjacent to the service ports for charging or recovering location and where
possible adjacent to existing nameplates or product information label.
2. Clearly write the charged refrigerant quantity on the refrigerant label using indelible ink. Then, place the
included transparent protective sheet over the label to prevent the writing from rubbing off.
3. Prevent emission of the contained uorinated greenhouse gas. Ensure that the uorinated greenhouse gas is
never vented to the atmosphere during installation, service or disposal. When any leakage of the contained
uorinated greenhouse gas is detected, the leak shall be stopped and repaired as soon as possible.
4. Only quali ed service personnel are allowed to access and service this product.
5. Any handling of the uorinated greenhouse gas in this product, such as when moving the product or recharging
the gas, shall comply under (EU) Regulation No. 517/2014 on certain uorinated greenhouse gases and any
relevant local legislation.
6. Periodical inspections for refrigerant leaks may be required depending on European or local legislation.
7. Contact dealers, installers, etc., for any questions.
Fully opened
– 16 –
R410A
2088 (ex.R410A ref.AR4)
EN
ID
ID
32-EN