Recommended Wire Length And Wire Diameter For Power Supply System - Panasonic U-8LE1R8 Installation Instructions Manual

Hide thumbs Also See for U-8LE1R8:
Table of Contents

Advertisement

4-2. Recommended Wire Length and Wire Diameter for Power Supply System

Outdoor unit
8 HP
10 HP
Indoor unit
(B) Power supply
Type
Minimum 2 mm²
K2
Max. 150 m
Y2
Max. 130 m
K1
U1
F2
T2
D1
L1
Z1
Control wiring
(C) Inter-unit (between outdoor and indoor units) control wiring
0.75 mm² (AWG #18)
Use shielded wiring*
Max. 1,000 m
* With ring-type wire terminal
N O T E
(E) Control wiring for group control
0.75 mm² (AWG #18)
Max. 200 m (Total)
(A) Power supply
Wire size
Max. length
4 mm²
57 m
4 mm²
50 m
Time delay fuse
2.5 mm²
circuit capacity
Max. 150 m
Max. 130 m
Max. 130 m
Max. 130 m
Max. 130 m
Max. 130 m
Max. 130 m
or
Time delay fuse or
circuit capacity
or
25 A
25 A
or
Type
15 A
M1
15 A
P1
10 – 16 A
R1
10 – 16 A
E1 (73)
10 – 16 A
E1 (106)
10 – 16 A
E1 (140)
10 – 16 A
E1 (224)
10 – 16 A
E1 (280)
10 – 16 A
E2
2.0 mm² (AWG #14)
Use shielded wiring*
Max. 2,000 m
25
(A) Power supply
Wire size
Max. length
6 mm²
86 m
6 mm²
75 m
(B) Power supply
Minimum 2 mm²
2.5 mm²
Max. 130 m
Max. 130 m
Max. 130 m
Max. 60 m
Max. 60 m
Max. 60 m
Max. 50 m
Max. 30 m
Max. 30 m
(D) Remote control wiring
0.75 mm² (AWG #18)
Max. 500 m
Time delay fuse or
circuit capacity
25 A
25 A
Time delay fuse
or
circuit capacity
10 – 16 A
10 – 16 A
10 – 16 A
10 – 16 A
10 – 16 A
10 – 16 A
10 – 16 A
10 – 16 A
10 – 16 A

Advertisement

Table of Contents
loading