Panasonic PAW-160MAH3M Installation Instructions Manual page 25

Air handling unit kit
Table of Contents

Advertisement

1
4
5
Control functions provided as standard by integral components
CZ-RTC6BL remote controller
● Operation-ON/OFF
● Mode selection
● Temperature setting
● Parameter settings
CZ-CAPBC2 Mini seri-para I/O unit
● Easy integration in external AHU control systems and BMS
● Demand control: 40 to 115 % (5 % steps) of nominal current by 0–10 V input signal
● Target temperature setting by 0–10 V or 0–140 Ω input signal1
● Suction air temperature (TA sensor) output by 4–20 mA signal
● Mode select and/or ON/OFF control
● Fan operation control
● Operation status output/ Alarm output
● Thermostat ON/OFF control
1 Demand control by external BMS cannot be combined with the demand control or target temperature setting accom-
plished by the integrated controller. However, if simultaneous demand control and target temperature setting is needed,
this can only be achieved by using a second (optional) CZ-CAPBC2 interface.
2 Mode select and/or ON/OFF control cannot be combined with fan operation control nor Thermostat ON/OFF control.
However, if simultaneous control of 2 options is needed, this can be achieved by using a second (optional) CZ-CAPBC2
interface. All 3 options cannot be used at the same time.
AHU Kit – Installation Instructions – 07/2023
> Terminals AI1, AI2.
> Terminals AI1, AI2.
> Terminals AO1, AO2.
> Terminals DI1, DI2, DI3, COM.
2
> Terminals DI1, DI2, DI3, COM.
> Terminals COM, DO1 / COM, DO2.
2
> Terminals DI1, DI2, DI3, COM.
PAW-280PAH3M-1
1
Remote controller (CZ-RTC6BL)
2
CZ-CAPBC2 interface
3
Main PCB
2
4
Fan relay
5
Terminal board
PACi and PACi NX accessories
3
NX
Thermistor x2
(Refrigerant: E1, E2)
2
Product description
Thermistor
(Air: TA)
1
25
3