4.7.3
N O T E
This function is only available for HC-A64NET units.
-
Enabled: enables the fan stop function
-
Master unit:
(Selected): CSNET Manager will only use this unit to calculate the temperature difference and decide the change, not
taking into account the other units connected to the same 2-tube cooling circuit.
(Not Selected): CSNET Manager will use the average temperature difference of all the indoor units connected to the same
2-tube cooling circuit.
-
Input data:
optional remote temperature sensor is connected in THM4 of the PCB of the indoor unit or if there is RCS remote sensor.
Status panel explain what is this function doing.
C A U T I O N
Fan stop heating during thermo off function is not compatible with CSNET WEB unit.
65
PMML0409A rev.1 - 10/2016