Hitachi CSNET MANAGER XT Installation And Operation Manual page 56

Table of Contents

Advertisement

different units.
Address
(note 1)
0
1
SYSTEM_ADDRESS
2
UNIT_ADDRESS
3
SET_ONOFF
4
SET_MODE
5
SET_FAN
6
SET_TSET
7
8
SET_CENTRAL
9
READ_ONOFF
10
READ_MODE
11
READ_FAN
12
READ_TSET
13
14
RCS_GROUP
15
16
50
PMML0409A rev.1 - 10/2016
Name
EXIST
TIN
TOUT
Description
0: Not exist
1: Exist
H-LINK 1: 0~15
H-LINK 2: 0~63
ON/OFF setting order:
0: Stop
1: Run
Mode setting order:
0: Cool
1: Dry
2: Fan
3: Heat
4: Auto
Fan setting order:
0: Low
1: Medium
2: High
Setting temperature
17ºC ~ 30ºC
Louver setting
0 ~ 7 (7 is Auto)
Central Setting:
Bit 0: ON/OFF (always can be stopped)
Bit 1: Mode
Bit 2: Setting temperature
Bit 3: Fan
Bit 4: Louver
ON/OFF read:
0: OFF
1: ON
Mode read:
0: Cool
1: Dry
2: Fan
3: Heat
4: Auto
Fan read
0: Low
1: Medium
2: High
Setting temperature read
(17ºC to 30ºC)
Louver read
0 ~ 7 (7 is Auto)
Remote controller group
0 ~ 255
Inlet temperature (Note 2)
Outlet temperature (Note 2)
R/W
R
R
R
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R
R
R
R
R
R