NetCol8000-C190 In-room Chilled Water Smart
Cooling Product
User Manual (2022, Singapore STT)
Figure 8-17 Setting alarm parameter 1
Step 2 Tap Threshold following Supply air high temperature alarm.
Step 3 Set the value to 45 and tap
Figure 8-18 Setting alarm parameter 2
----End

8.4.14 How to Commission Single Component

Context
Procedure
Step 1 Choose Maint > Diagnostic Mode > Enter.
Issue 02 (2022-03-30)
On the diagnostic mode screen, you can turn on or off components, and
control their output ratio.
If you need to manually turn on or off system components in diagnostic
mode, ensure that the smart cooling product is started before operation.
Take commissioning the indoor fan as an example.
Copyright © Huawei Technologies Co., Ltd.
, as shown in
Figure
8-18.
8 FAQ
134