ABB SACE Emax 2 Series Operating Instructions Manual page 202

Low voltage air circuit-breaker
Table of Contents

Advertisement

AUP: auxiliary position
contacts
199 | © 2023 ABB | 1SDH001330R1002 - ECN000297030
The AUP contacts are intended for circuit-breakers in withdrawable version.
They electrically signal the position of a moving part (inserted/test/withdrawn) in relation to the fixed
part in which they are inserted.
These are "switching" contacts and are available in the following configurations:
Up to a maximum of six contacts for E1.2:
• six standard contacts
• six digital signals
Up to a maximum of ten contacts for E2.2-E4.2-E6.2:
• five standard contacts
• five digital signals
• five additional standard contacts
• five additional digital signals
AUP for E1.2
The following table provides information on the electrical characteristics:
Characteristics
24V
DC
125V
250V
Breaking
250V
capacity
AC
400V
Minimum load
AUP: Connections
More details are available in the website http://www.abb.com/abblibrary/DownloadCenter/, which also
includes the entire circuit diagram 1SDM000091r0001.
Information on the assembly is available on the website http://www.abb.com/abblibrary/
DownloadCenter/, in particular for E1.2 in the kit sheet
kit sheet 1SDH001000r0603.
AUP for E2.2 - E4.2 - E6.2
Standard
-
0.5A @ 0ms / 0.3A @ 10ms
0.3A @ 0ms / 0.15A @ 10ms
3A cosφ 0,3
5A cosφ 0,7
5A cosφ 1
3A cosφ 1
2A cosφ 0,7
1A cosφ 0,3
100mA @ 24V
1SDH000999r0603
2 - Electrical signalling accessories
ABB | SACE Emax 2
Digital signals
0.1 A
-
-
-
-
-
-
-
-
1mA @ 5V
and for E2.2-E4.2-E6.2 in the
Electrical accessories