Siemens SINAMICS S120 Equipment Manual page 236

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line Modules Booksize
3.4 Basic Line Modules with internal air cooling
A ventilation clearance of 80 mm above and below the components must be observed.
It is only permissible to establish connections to the DC link using the adapters that
SIEMENS has recommended (DC link adapter and DC link rectifier adapter).
CAUTION
The connection to the braking resistors must be made using a shielded cable.
The tightening torque of the DC link busbar screws (1.8 Nm, tolerance +30 %) must be
checked before commissioning. After transportation, the screws must be tightened.
NOTICE
The electronics of the braking module is powered from the DC link. That means, as long as
there is no DC link voltage (< 360 V ± 2 %), the electronics are not active and an external
control or the CU320 receives the signal "fault" from the fault output. So more than the
2 seconds are required that the electronics requires to start up as soon as the DC link
voltage is present.
Note
If braking resistors other than those listed in the operating instructions, order number
6SE7087-6CX87-2DA1, are used, they may be damaged.
236