Huawei LUNA2000-200KTL-H0 User Manual page 67

Smart power control system
Table of Contents

Advertisement

LUNA2000-200KTL-H0 Smart Power Control System
User Manual
No.
Category
15
Hibernate at
night
16
Upgrade delay
17
HVRT/LVRT
18
Issue 05 (2022-06-30)
Parameter
Description
Hibernate at
The device performs the
night
monitoring function at night.
If this parameter is set to
Enable, the monitoring
function of the device will
hibernate at night to reduce
power consumption.
Upgrade delay
This parameter is mainly used
in upgrade scenarios where
the power supply at DC side
is disconnected.
HVRT
HVRT is short for high
voltage ride-through. When
the grid voltage is abnormally
high for a short time, the
device cannot disconnect
from the power grid
immediately and must
continue to operate for some
time.
HVRT triggering
Specifies the threshold for
threshold (V)
triggering HVRT. The
threshold settings should
meet the local grid standard.
Copyright © Huawei Technologies Co., Ltd.
8 Device Commissioning
Remarks
-
After the upgrade
starts, if Upgrade
delay is set to
Enable, the upgrade
package is loaded
first. After the DC
side power supply
recovers and the
activation conditions
are met, the device
automatically
activates the
upgrade.
-
This parameter is
displayed when
HVRT is set to
Enable.
-
This parameter is
displayed when
LVRT is set to
Enable.
61

Advertisement

Table of Contents
loading

Table of Contents