Download Print this page

Siemens LMV5 Series Manual page 7

Burner management system
Hide thumbs Also See for LMV5 Series:

Advertisement

Technical data
LMV5
Building Technologies Division
Mains voltage
Note!
Only for use in earthed networks!
Transformer
- Primary side
- Secondary side 1
- Secondary side 2
Mains frequency
Power consumption
Safety class
Terminal loading «Inputs»
Perm. mains primary fuse
(externally)
Unit fuse F1 (internally)
Mains supply: Input current depending on operating state of the unit
Undervoltage
Safety shutdown from operating
position at mains voltage
Restart on rise in mains voltage
Oil pump / magnetic clutch
(nominal voltage)
Nominal current
Power factor
Air pressure switch test valve (nominal
voltage)
Nominal current
Power factor
Status inputs (KRN): Status inputs (with the exception of the safety loop) of the
contact feedback network (CFN) are used for system supervision and require mains-
related input voltage
Input safety loop
Input currents and input voltages
- UeMax
- UeMin
- IeMax
- IeMin
Contact material recommendation
for external signal sources (LP,
DWmin, DWmax, etc.)
Transition / settling behavior /
bounce
- Perm. bounce time of contacts
when switching on / off
UN
Voltage detection
- On
- Off
Terminal loading «Outputs»
Total contact loading:
(nominal voltage)
Unit input current (safety loop) total
contact current from:
- Fan motor contactor
- Ignition transformer
- Valves
- Oil pump / magnetic clutch
AC 120 V
AC 230 V
-15% / +10%
-15% / +10%
AGG5.210
AGG5.220
AC 120 V
AC 230 V
12 V~
12 V~
2 x 12 V~
2 x 12 V~
50 / 60 Hz ±6%
50 / 60 Hz ±6%
<30 W (typically)
<30 W (typically)
I, with parts according to II and III to
DIN EN 60730-1
Max. 16 AT
Max. 16 AT
6.3 AT to
6.3 AT to
DIN EN 60127 2/5
DIN EN 60127 2/5
<96 V~
<186 V~
>100 V~
>188 V~
1,6 A
2 A
Cos >0.4
Cos >0.4
0.5 A
0.5 A
Cos >0.4
Cos >0.4
Refer to «Terminal loading outputs»
UN +10%
UN +10%
UN -15%
UN -15%
1.5 mA peak
1.5 mA peak
0.7 mA peak
0.7 mA peak
Gold-plated silver contacts
Max. 50 ms
(after the bounce time, the contact must
stay closed or open)
AC 120 V
AC 230 V
90...132 V~
180...253 V~
<40 V~
<80 V~
AC 120 V
AC 230 V
-15 % / +10 %
-15 % / +10 %
Max. 5 A
Max. 5 A
7/29
CC1N7550en
22.05.2017

Advertisement

loading