Siemens LMV5 Series Manual page 6

Burner management system
Hide thumbs Also See for LMV5 Series:

Advertisement

Mechanical design (cont'd)
Type summary
AC 230 V LMV50
LMV50.320B2
AC 230 V Europe
LMV51.000C2
AC 120 V US / Canada
LMV51.040C1
AC 120 V Europe
LMV51.100C1
AC 230 V Europe
LMV51.100C2
AC 120 V US / Canada
LMV51.140C1
AC 120 V Europe
LMV51.300B1
AC 230 V Europe
LMV51.300B2
AC 120 V US / Canada
LMV51.340B1
AC 120 V Europe
LMV52.200B1
AC 230 V Europe
LMV52.200B2
AC 120 V US / Canada
LMV52.240B1
AC 230 V US / Canada
LMV52.240B2
AC 230 V Europe
LMV52.400B2
AC 120 V US / Canada
LMV52.440B1
**)
6/29
Building Technologies Division
When designing the fuel trains, the burner / boiler manufacturer can choose from a total
of 7 valve families. The large number of individual parameterization choices (program
times, configuration of inputs / outputs, etc.) enable him to make optimum adaptions to
the specific application.
The universal SQM4 / SQM9 actuators are driven by stepper motors and can be
positioned with high resolution. The characteristics and settings of the actuators are
defined by the LMV5.
5 *)
4
4
4
4
4
5 *)
5 *)
5 *)
6
6
6
6
6
6
*) When the VSD module is activated, only 4 SQM4/SQM9 actuators can be controlled!
Attention!
The maximum safety time in the parameter set is set as follows ex works:
Gas
Parameter set
LMV50
10 s
Europe
3 s
US / Canada
10 s
On the OEM access level, it is possible to make parameter settings that differ
from application standards. For this reason, check whether the parameter
settings made are in compliance with the application standards (e.g. EN 676, EN
267, etc.), or whether the respective plant requires special approval!
---
---
---
---
---
---
---
---
---
Oil
10 s
5 s
15 s
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
CC1N7550en
22.05.2017
**)
Gas
Oil
10 s 15 s
10 s 15 s
10 s 15 s
10 s 15 s
10 s 15 s
10 s 15 s
10 s 15 s
10 s 15 s
10 s 15 s
10 s 15 s
10 s 15 s
10 s 15 s
10 s 15 s
10 s 15 s
10 s 15 s