Panasonic WH-ADC0509L3E5 Installation Manual page 6

Hide thumbs Also See for WH-ADC0509L3E5:
Table of Contents

Advertisement

(C) Domestic Hot Water Tank Pipework
It's strongly recommended to install an expansion vessel (fi eld supply) in the
Domestic Hot Water Tank circuit. Refer Typical Piping Installation section to
locate the expansion vessel.
Recommended pre-charge pressure of the expansion vessel (fi eld supply)
= 3.5bar (0.35MPa)
In high water pressure or water supply is above 5bar, please install the Pressure
Reducing Valve for water supply. If the pressure higher than that, it might
damage the Tank Unit.
A Pressure Reducing Valve (fi eld supply) with below specifi cation is strongly
advised to be installed along the line of the tube connector i of Tank Unit. Refer
Typical Piping Installation section to locate both of these valves.
Recommended Pressure Reducing Valve specifi cations:
- Set pressure: 3.5bar (0.35MPa)
Must connect a faucet to Tank Unit Tube Connector j and main water supply,
in order to supply water with appropriate temperature for shower or tap usage.
Failure to do so might cause scalding.
Failure to connect the tube appropriately might causing the Tank Unit malfunction.
(D) Drain Elbow and Hose Installation
Fix the Drain Elbow 2 and Packing 3 to the bottom of Drain Water Hole
Packing
Drain Elbow
Use inner diameter 17 mm drain hose in the market, fi x to Drain Elbow 2 .
This hose must to be installed in a continuously downward direction and in a
frost-free environment. Improper drain piping may cause water leakage hence
damage the furnitures.
If drain hose is long, use a metal support fi xture along the way to eliminate the
wavy pattern of drain tube.
Guide the drain hose to outdoor as illustrated.
Illustration of guide drain hose to outdoor
Do not insert this hose into sewage or drain pipe that may generate ammonia
gas, sulphuric gas etc.
If necessary, use hose clamp to further tighten the hose at drain hose connector
to prevent leakage.
Water will drip from this hose, therefore the outlet of this hose must be installed
in an area where the outlet cannot become blocked.
If drain hose is in the room (where dew may form), please increase the insulation
by using POLY-E FOAM with thickness 6 mm or above.
(E) Domestic Hot Water Tank Discharge (Drain Tap) and Safety Relief
Valve Pipework
Safety Relief Valve 8bar (0.8MPa) incorporated in Domestic Hot Water Tank.
Drain Tap and Safety Relief Valve discharge fi ttings share the same drainage outlet.
Use R½" male connector for this drainage outlet connection (Tube connector
Piping must always be installed in a continuously downward direction. It must not
be longer than 2m, with no more than 2 elbows, and must not allow condensation
to build up or freezing to occur.
The pipe from this drainage outlet fi tting must not be shut off. The discharge
must be freed.
The end of this pipework must be in such a way so that the outlet is visible and can
not cause any damage. Keep away from electrical components.
It is recommended to fi t a tundish into this
and positioned away from frost environment and electrical components.
CONNECT THE CABLE TO
4
THE TANK UNIT
This section is for authorized and licensed electrician only. Work
behind the Control Board Cover 5 secured by screws must
only be carried out under supervision of qualifi ed contractor,
installation engineer or service person.
6
3
2
Discharge below
fi xed grating
Fixed grating
Trapped gulley
Possible wall
g
pipework. Tundish should be visible
WARNING
Please take extra precaution when open
the control board cover 5 and control
board 6 for unit installation and servicing.
Failure to do so may cause injury.
Fixing of Power Supply Cable and Connecting Cable
1. Connecting cable between Tank Unit and Outdoor Unit shall be approved
polychloroprene sheathed fl exible cord, type designation 60245 IEC 57
or heavier cord. See below table for cable size requirement.
Tank Unit
WH-ADC0509L3E5,
.
h
WH-ADC0509L3E5AN,
WH-ADC0509L6E5,
WH-ADC0509L6E5AN
Ensure the colour of wires of Outdoor Unit and the terminal no.
are the same to the Tank Unit respectively.
Earth wire shall be longer than the other wires as shown in the
fi gure for the electrical safety in case of the slipping out of the
cord from the Holder (Clamper).
2. An isolating device must be connected to the power supply cable.
Isolating device (disconnecting means) should have minimum
3.0 mm contact gap.
Connect the approved polychloroprene sheathed power
supply 1 cord and power supply 2 cord and type designation
60245 IEC 57 or heavier cord to the terminal board, and to the
other end of the cord to isolating device (Disconnecting means).
See below table for cable size requirement.
Model
Tank Unit
Outdoor Unit
WH-WDG05LE5*
WH-ADC0509L3E5,
WH-WDG07LE5*
WH-ADC0509L3E5AN
WH-WDG09LE5*
WH-WDG05LE5*
WH-ADC0509L6E5,
WH-WDG07LE5*
WH-ADC0509L6E5AN
WH-WDG09LE5*
3. To avoid the cable and cord being damaged by sharp edges, the
cable and cord must be passed through a bushing (located at the
bottom of Control Board 6) before terminal board. The bushing
must be used and must not be removed.
Terminals on the Outdoor Unit
Colour of wires (Connecting cables)
Terminals on the Tank unit
(Power Supply Cord)
Terminals on the isolating devices
g
).
from power supply (Disconnecting
means)
RCCB/ELCB
*1
Holder
(Clamper)
Power Supply 1 Cable
Terminal screw
M4
M5
*1 - Earth wire must be longer than other cables for safety reasons
CAUTION
Model
Outdoor Unit
WH-WDG05LE5*
WH-WDG07LE5*
WH-WDG09LE5*
Power
Isolating
Supply
Cable Size
Devices
Cord
1
3 x min 2.5 mm
2
25A
2
2
3 x min 1.5 mm
15/16A 30mA, 2P, type AC
1
3 x min 2.5 mm
2
25A
2
2
3 x min 4.0 mm
30A
L
N
L
N
1
1
L
N
L
N
1
1
Power Supply 1 Power Supply 2
Holder
(Clamper)
Power Supply 2 Cable
Connecting Cable
Tightening torque cN•m {kgf•cm}
157~196 {16~20}
196~245 {20~25}
Connecting Cable
Size
4 x min 2.5 mm
2
Recommended
RCD
30mA, 2P, type A
30mA, 2P, type A
30mA, 2P, type AC
1
2
3
1
2
3
Tank Unit/
Outdoor Unit
connection
Terminal
Board
*1