Access to Internal Components
This section is for authorized and licensed electrician/water system
installer only. Work behind the front plate secured by screws
must only be carried out under supervision of qualifi ed contractor,
installation engineer or service person.
Hook
Open or close the Front Plate carefully.
The heavy Front Plate may injures the
fi ngers.
* The remote control cable is connected
to the front panel, so be careful when
removing the panel.
2X (screw)
Open and Close Front Plate h
1. Remove the 2 mounting screws of Front Plate h.
2. Slide it upwards to unhook the Front Plate h hook.
3. Reverse above steps 1~2 for close it.
Water Piping Installation
Please engage a licensed water circuit installer to install this
water circuit.
This water circuit must comply with relevant European and national
regulations (including EN61770), and local building regulation
codes.
Ensure the components installed in the water circuit could withstand
water pressure during operation.
Do not use worn out tube or detachable hose-set.
Do not apply excessive force to pipes that may damage the pipes.
Choose proper sealer which can withstand the pressures and
temperatures of the system.
Make sure to use two spanners to tighten the connection. Further
tighten the nuts with torque wrench in specifi ed torque as stated
in the table.
Cover the pipe end to prevent dirt and dust when inserting it
through a wall.
If non-brass metallic piping is used for installation, make sure to
insulate the pipes to prevent galvanic corrosion.
Do not connect galvanised pipes, this will cause galvanic corrosion.
Use correct nut for all Tank Unit tube connections and clean
all tubes with tap water before installation. See Tube Position
Diagram for detail.
Tube Connector
a
b
&
c
d
&
e
f
&
Torque wrench Spanner
WARNING
CAUTION
Nut Size
Torque
RP 1¼"
117.6 N•m
RP ¾"
58.8 N•m
RP 1"
88.2 N•m
Do not overtighten, overtightening may cause water leakage.
Make sure to insulate the water circuit pipes to prevent reduction
of heating capacity.
After installation, check the water leakage condition in connection
area during test run.
Failure to connect the tube appropriately might cause the Tank
Unit malfunction.
Protection From Frost:
If the Tank Unit is being exposed to frost while power supply failure
or pump operating failure, drain the system. When water is idle
inside the system, freezing up is very likely to happen which could
damage the system. Make sure the power supply is turned off before
draining. Heater Assembly 0 may be damaged under dry heating.
Corrosion Resistance:
Duplex stainless steel is naturally corrosion resistant to mains
water supply. No specifi c maintenance is required to maintain this
resistance. However, please note that Tank Unit is not guaranteed
for use with a private water supply.
It is recommended to use a tray (fi eld supply) to collect water from
the Tank Unit if water leakage occur.
Recommended piping installation sequence:
(a)  (c)  (e)  (f)  (b)  (d)
(A) Space Heating/Cooling Pipework
Connect Tank Unit Tube Connector
Panel/Floor heater.
Connect Tank Unit Tube Connector
Panel/Floor heater.
Failure to connect the tube appropriately might cause the Tank
Unit malfunction.
Refer below table for the rated fl ow rate of each particular
Outdoor Unit.
Model
WH-ADC0509L3E5,
WH-WDG05LE5*
WH-ADC0509L3E5AN,
WH-WDG07LE5*
WH-ADC0509L6E5,
WH-WDG09LE5*
WH-ADC0509L6E5AN
* Do not install automatic air purge valves on indoor water pipes.
In the unlikely event that the R290 refrigerant leaks into the
water circuit, there is a risk that the refrigerant will leak indoors.
(B) Circulating Pipework
Connect Tank unit Tube Connector
socket.
Connect Tank Unit Tube Connector
socket.
Failure to connect results in an error stop the system.
Water piping between outdoor unit and indoor unit
Model
Inner
diameter
WH-WDG05LE5*
ø20
WH-WDG07LE5*
ø25
WH-WDG09LE5*
CAUTION
to outlet connector of Zone 1
a
to inlet connector of Zone 1
b
Rated Flow Rate (l/min)
Cool
14.3
20.1
23.5
f
to outdoor unit inlet water
e
to Outdoor unit outlet water
Maximum
Insulator
Maximum
length
thickness
Elevation
30 mm
30 m
or more
Heat
14.3
20.1
25.8
10 m
5