1-1-2.
EXTERNAL OUTPUT
Connector
CN136 (Black)
CN137 (Blue)
ERROR STATUS (Master unit only)
This output indicates the outdoor unit and connected indoor unit's "Normal" or "Error" status.
OPERATION STATUS (Master unit only)
This output indicates the outdoor unit's "Operation" status.
P.C.B
+
CN136
(Black)
1
or CN137
(Blue)
2
-
*6
Operation
Stop
CN137
Output
12 - 24V
0V
Error
CN136
Normal
Output
12 - 24V
0V
*A twisted pair cable (22AWG) should be used. Maximum length of cable is 150m.
* Use an external input and output cable with appropriate external dimension, depending on the
number of cables to be installed.
BASE HEATER
This is the output signal for base heater. Output signal ON, when the outdoor temperature
goes down below 2°C, and signal OFF at the outdoor temperature 4°C.
P.C.B
1
2
CN115
(Black)
3
*7
4
*7: Connect to pin 1 and pin 3. No connection pin2 and pin4.
*8: The allowable current is 1A or less.
Output voltage
0V
DC 12-24 V *4
0V
DC 12-24 V *4
DC power supply
(External) 12 - 24V
+
-
Connected
load (Operation
Indicator or Error
Indicator)
connected unit
Voltage: power supply
input voltage
2
AWG18 (0.82mm
)
- (08 - 05) -
Status
Normal
Error
Stop
Operation
*4: Provide a DC12 to 24V power supply.
Select a power supply capacity with an ample
*4
surplus for the connected load.
*5: The allowable current is 30mA or less.
Provide a load resistance such that the current
becomes 30mA or less.
*6: Polarity is [+] for pin 1 and [-] for pin 2.
Connect correctly.
Do not impress a voltage exceeding 24V across
*5
pins 1-2.
Base heater
*8

Advertisement