Signal Amplifier - Fujitsu AIRSTAGE J-II Design & Technical Manual

Hide thumbs Also See for AIRSTAGE J-II:
Table of Contents

Advertisement

3-4.

SIGNAL AMPLIFIER

MODEL : UTY - VSGXZ1
If the total length of transmission line exceeds 500 m, or the number of elements exceeds 64
units, Signal Amplifier will be necessary to use.
Transmission line length can be extended up to 3600 m with multiple signal amplifier.
Up to 8 Signal Amplifier (Filter mode is OFF) can be installed in 1 VRF network system.
Up to 32 Signal Amplifier (Filter mode is ON) can be installed in 1 VRF network system.
When installing 321 or more indoor units, install 1 Signal amplifier (Filter mode is ON) for every 64
indoor units. (However, only when VR-II Series is installed.)
FEATURES
To prevent the drop of signal level by taking distance of length or quantity of unit in VRF
network with installing signal amplifier, signal level can be recovered.
ELECTRICAL WIRING
Case of V-II or J-II or VR-II
z
1Ø 50 Hz
220-240 V
SWITCH
INDOOR UNIT
TRANS-
MISSION
TERMINAL
RESISTOR*
(DIP SW setting)
X1
X2
IN/U-
OUT/U
(Indoor unit is installed 320 units or less)
FUSE (3 A)
POWER
SUPPLY
L
N
X1 X2
Z1 Z2
H1 H2
OTHER
MULTI
CYCLE
OUT/U
OUTDOOR UNIT
(MASTER UNIT)
- (05 - 120) -
Segment B
Segment A
SIGNAL AMPLIFIER
NO HIGH VOLTAGE
TRANSMISSION
CH A
CH B
X1
X2
X1 X2
TERMINAL
RESISTOR*
TO SLAVE
UNIT
INDOOR UNIT
TRANS-
MISSION
X1 X2
Transmission Line

Advertisement

Table of Contents
loading

Table of Contents