Additional Charge Calculation - Fujitsu AIRSTAGE J-II Design & Technical Manual

Hide thumbs Also See for AIRSTAGE J-II:
Table of Contents

Advertisement

2-5.

ADDITIONAL CHARGE CALCULATION

The outdoor unit is charged refrigerant at the factory.
Additional refrigerant required to be charged on site depending on pipe length.
The additional refrigerant charge amount is calculated according to the following formula.
Round up the calculated result to two decimal places.
CALCULATION OF ADDITIONAL CHARGE REFRIGERANT
1. Calculation of additional amount for outdoor unit
Model
HP
AJ  A40LALH
4
AJ  A45LALH
5
AJ  A54LALH
6
2. Calculation of additional amount for pipe length
Total
a :
length of
ø9.52mm
x 0.058
A=
liquid pipe
kg/m
m
3. Calculation of additional charge refrigerant
kg
A =
4. Factory charged amount
b : Outdoor unit
factory charged amount
B=
5. Total refrigerant amount check
C = A + B =
Note : Check the total refrigerant amount under the following conditions.
Total amount of refrigerant ≤ 15.70kg
When total refrigerant amount exceed limitation.
Reduce pipe length for refrigerant system.
Change the refrigerant system configuration.
b
Diameter of liquid
Factory charged
amount (kg)
4.80
5.30
5.30
Total
a :
length of
ø6.35mm
x 0.021
+
liquid pipe
kg/m
m
kg
Round up A to 2 decimal place.
kg
kg
Condition
- (06 - 22) -
Additional amount for
pipe (mm)
pipe length (kg/m)
ø6.35
0.021
ø9.52
0.058
Total
=
kg
kg
a
Computational formula
C ≤ 15.70kg