ADDITIONAL CHARGE CALCULATION
●
The outdoor unit is charged refrigerant at the factory.
●
Additional refrigerant required to be charged on site depending on pipe length.
●
The additional refrigerant charge amount is calculated according to the following formula.
●
Round up the calculated result to two decimal places.
CALCULATION OF ADDITIONAL CHARGE REFRIGERANT
1. Calculation of additional amount for outdoor unit
Model
HP
AJ A40LALH
4
AJ A45LALH
5
AJ A54LALH
6
2. Calculation of additional amount for pipe length
Total
a :
length of
ø9.52mm
x 0.058
A=
liquid pipe
kg/m
m
3. Calculation of additional charge refrigerant
kg
A =
4. Factory charged amount
b : Outdoor unit
factory charged amount
B=
5. Total refrigerant amount check
C = A + B =
Note : Check the total refrigerant amount under the following conditions.
Total amount of refrigerant ≤ 15.70kg
When total refrigerant amount exceed limitation.
●
Reduce pipe length for refrigerant system.
●
Change the refrigerant system configuration.
b
Diameter of liquid
Factory charged
amount (kg)
4.80
5.30
5.30
Total
a :
length of
ø6.35mm
x 0.021
+
liquid pipe
kg/m
m
kg
Round up A to 2 decimal place.
kg
kg
Condition
- (06 - 22) -
Additional amount for
pipe (mm)
pipe length (kg/m)
ø6.35
0.021
ø9.52
0.058
Total
=
kg
kg
a
Computational formula
C ≤ 15.70kg