5 Level 2 Access

At this level the operator is expected to have under gone training so as to be able to;
➢ test crucial elements of the system and;
➢ isolate dedicated facilities that may be in fault.
In the Main Menu From FAULTS Move Right for TEST

5.1 Tests

Press Enter to access the available menus
The available menus are;
Alarm Test
Note: The Sounder Test Menu is only displayed if it is installed and set to active in the System
Menu.
To initiate one of the above tests press the Move Right / Move Left key to move through the menu.
Press Enter, then select the Zone by using the Move Up and / or Move Down keys until the desired
Zone number is displayed, press Enter to start the test.
Alarm Test of each Zone
Once the test is commenced the Buzzer will turn on and off and the common Alarm and Zone Alarm
LED's will flash. Press Acknowledge, the Buzzer will be silenced and the common Alarm and Zone Alarm
LED's will be steady. Press Reset to return the panel to normal. The LCD will indicate the alarm has
occurred and then toggle to display the Zone and descriptor of that Zone.
Note: If a Zone has been programmed to be;
1.
NON LATCHING the panel will only go into alarm for 5 seconds and then automatically reset.
2.
Self Resetting ( SREST 60) the panel will go into alarm for 60 seconds and then automatically reset.
Fault Test
Walk Test
ALRM TST
ZONE 1
Alarm LCD Sequence
Lamp Test
ALARM
OCCURRED
MAN1564-3
TEST
ISOLATE
Battery Test
Sounder Test
Z1 : LOBBY
15