Installation
Fig. 18 Fit mounting rails and connection plate
▶ Fit the pipes with gaskets to the mounting plate.
Fig. 19 Fitting the pipes with gaskets to the mounting plate
6.3.2

Installing the appliance

Removing the casing (see packaging)
▶ Remove the locking bracket.
Hanging the appliance
▶ Fit the sealing washers to service valves.
▶ Hang the appliance.
▶ Unlock the condensate trap and remove from appliance ( Fig.
9.17, p. 46)
▶ Check the positioning of the sealing washers on the pipe
connections.
▶ Tighten the union nuts on the pipe connections starting with the CH
return on the right.
18
6.4

Hydraulic connection

Preparing the pipework
Residues in the pipework can damage the device.
▶ Purge the pipework prior to connection.
Fitting a pipe to the pressure relief valve
Fig. 20 Fitting a pipe on the pressure relief valve
Connecting the condensate pipes
0010041048-002
▶ Insert the condensate pipe hose into the mounting plate (1).
▶ Insert the condensate hose on the connector (2).
0010041049-002
Fig. 21 Fitting the condensate pipes to the mounting plate
0010041319-001
0010034879-002