Typical Power Cable Sizes - ABB ACS560 Hardware Manual

0.75 to 160 kw, 1.0 to 215 hp
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

Cross-sectional area of the phase conduct-
S (mm 2 )
Note: See the IEC/EN 61800-5-1 requirement on grounding in the Note on section
Grounding.

Typical power cable sizes

The table below gives copper cable types with concentric copper shield for the
drives with nominal current. The value separated by the plus sign means the
diameter of the PE conductor.
Drive type
Framesize
ACS560
3-phase U N = 400 V (380...480 V)
02A6-4
03A3-4
04A0-4
05A6-4
07A2-4
09A4-4
12A6-4
017A-4
025A-4
033A-4
039A-4
046A-4
062A-4
073A-4
088A-4
106A-4
145A-4
169A-4
206A-4
246A-4
ors
35 < S
Cu cable type
mm 2
R0
3 x 1.5 + 1.5
R0
3 x 1.5 + 1.5
R0
3 x 1.5 + 1.5
R0
3 x 1.5 + 1.5
R0
3 x 1.5 + 1.5
R0
3 x 2.5 + 2.5
R1
3 x 2.5 + 2.5
R2
3 x 2.5 + 2.5
R2
3 x 6 + 6
R3
3 x 10 + 10
R3
3 x 10 + 10
R3
3 x 16 + 16
R4
3 x 25 + 16
R4
3 x 35 + 16
R5
3 x 35 + 16
R5
3 x 50 + 25
R6
3 x 95 + 50
R7
3 x 120 + 70
R7
3 x 150 + 70
R8
2 x (3 x 70 +
35)
Planning the electrical installation 69
Minimum cross-sectional area of the corres-
ponding protective conductor
1)
IEC
Cu cable type
AI cable
2)
type
mm 2
-
-
-
-
-
-
-
-
-
-
-
-
3 x 35
3 x 50
3 x 70
3 x 70
3 x 120
3 x 150
3 x 240
2 x (3 x 95)
S p (mm 2 )
S/2
US
AI cable
type
AWG/kcmil
AWG/kcmil
16
16
16
16
16
14
14
14
10
8
8
6
4
2
2
1/0
3/0
250 MCM
300 MCM
2 x 2/0
3)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-